.
OVERVIEW:
1 Underground System Designs
2 Conductor
3 Insulation
4 Medium- and High-Voltage Power Cables
5 Shield Bonding Practice
6 Installation Practice
7 System Protection Devices
8 Common Calculations Used with Cable
Aesthetics is primarily the major reason for installing power cables underground,
providing open views of the landscape free of poles and wires. One could also
argue that underground lines are more reliable than overhead lines as they
are not susceptible to weather and tree caused outages, common to overhead
power lines. This is particularly true of temporary outages caused by wind,
which represents approximately 80% of all outages occurring on overhead systems.
However, underground lines are susceptible to being damaged by excavations
(reason behind "call before digging" locating programs implemented
by many states in the United States). The time required to repair a damaged
underground line may be considerably longer than an overhead line. Underground
lines are typically 10 times more expensive to install than overhead lines.
The ampacity, current carrying capacity, of an underground line is less than
an equivalent sized overhead line. Underground lines require a higher degree
of planning than over head, because it’s costly to add or change facilities
in an existing system. Underground cables don’t have an infinite life, because
the dielectric insulation is subjected to aging; therefore, systems should
be designed with future replacement or repair as a consideration.
========
Source Circuit breaker or load switch
Transformer Source 1
(A)
(B)
Source 2 Circuit breaker or load switch
Circuit breaker or load switch Transformer Open

Above: Fig. 1 (A) Radial system and (B) looped system.
========
1 Underground System Designs
There are two types of underground systems ( FIG. 1).
1. Radial-Where the transformers are served from a single source.
2. Looped-Where the transformers are capable of being served from one of two
sources. During normal operation an open is located at one of the transformers,
usually the midpoint.
A radial system has the lowest initial cost, because a looped system requires
the additional facilities to the second source. Outage restoration on a radial
system requires either a cable repair or replacement, whereas on a looped system,
switching to the alternate source is all that is required.
Underground cable can be directly buried in earth, which is the lowest initial
cost, allows splicing at the point of failure as a repair option and allows
for maximum ampacity. Cables may also be installed in conduit, which is an
additional cost, requires replacement of a complete section as the repair option,
reduces the ampacity, because the conduit wall and surrounding air are additional
thermal resistances, but provides protection to the cable.
Underground power cables have three classifications.
1. Low voltage-Limited to 2 kV. Primarily used as service cables
2. Medium voltage-2-46 kV. Primarily used to supply distribution transformers
3. High voltage-Above 46 kV. Primarily used to supply substation transformers
American Standards Testing Material (ASTM), Insulated Cable Engineering Association
(ICEA), National Electrical Manufacturing Association (NEMA), and Association
of Edison Illuminating Companies (AEIC) have published standards for the various
types of power cables.
2 Conductor
Common among all classes in function is the central conductor, the purpose
of which is to conduct power (current and voltage) to serve a load. The metals
of choice are either copper or aluminum. This central conductor may be composed
of a single element (solid) or composed of multiple elements (stranded), on
the basis of a geometric progression of 6, 12, 18, etc., of individual strands
for each layer.
Each layer is helically applied in the opposite direction of the underlying
layer.
There are three common types of stranding available.
1. Concentric round
2. Compressed round (97% of the diameter of concentric)
3. Compact round (90%-91% of the diameter of concentric)
Note: Some types of connectors may be suitable for stranded types 1 and 2
but not type 3 for the same size.
To improve manufacturing, 19 wire combination unilay stranding (helically
applied in one direction one operation) has become popular in low-voltage applications,
where some of the outer strands are of a smaller diameter, but the same outside
diameter as compressed round is retained. Another stranding method which retains
the same overall diameter is single input wire (SIW) compressed, which can
be used to produce a wide range of conductors using a smaller range of the
individual strands.
Conductors used at transmission voltages may have exotic stranding to reduce
the voltage stress.
Cables requiring greater flexibility such as portable power cable utilize
very fine strands with a rope type stranding.
Typical sizes for power conductors are #6 American wire gage (AWG) through
1000 kcmil. One cmil is defined as the area of a circle having a diameter of
1 mile (0.0001 in.). Solid conductors are usually limited to a maximum of #1/0
because of flexibility.
The metal type and size determines the ampacity and losses (I2 R). Copper
having a higher intrinsic conductivity will have a greater ampacity and lower
resistance than an equivalent size aluminum conductor. Aluminum 1350 alloy
medium hardness is typical for power cable use.
3 Insulation
In order to install power cables underground, the conductor must be insulated.
For low-voltage applications, a layer of insulation is extruded onto the conductor.
Many types of insulation compounds have been used from natural or synthetic
rubber, polyvinyl chloride (PVC), high molecular weight polyethylene (HMWPE),
and cross-linked polyethylene (XLPE) to name a few. Although each insulation
type has various characteristics, operating temperature and durability are
probably the most important. XLPE is probably the most widely used insulation
for low-voltage cables. XLPE is a thermoset plastic with its hydrocarbon molecular
chains cross-linked. Cross-linking is a curing process, which occurs under
heat and pressure, or as used for low-voltage cables, moisture and allows an
operating temperature of 90°C.
Multiple layer cable insulation composed of a softer compound under a harder
compound, a single layer harder insulation, or a self-healing insulation are
used to address protection of the conductor, typically for direct buried low-voltage
power cables.

Above: Fig. 2 (A) Medium-voltage cable components and (B) high-voltage cable
components.

Above: Fig. 3 Tree in XLPE.
4 Medium- and High-Voltage Power Cables
Medium- and high-voltage power cables, in addition to being insulated, are
shielded to contain and evenly distribute the electric field within the insulation.
The components and function of a medium- and high-voltage cable are as follows
( FIG. 2A and B):
1. The center conductor-Metallic path to carry power.
2. The conductor shield-A semiconducting layer placed over the conductor to
provide a smooth conducting cylinder around the conductor. Typical of today's
cables, this layer is a semiconducting plastic, polymer with a carbon filler,
extruded directly over the conductor. This layer represents a very smooth surface,
which, because of direct contact with the conductor, is elevated to the applied
voltage on the conductor.
3. The insulation-A high dielectric material to isolate the conductor. The
two basic types used today are XLPE or ethylene propylene rubber (EPR). Because
of an aging effect known as treeing ( FIG. 3), on the basis of its visual appearance,
caused by moisture in the presence of an electric field, a modified version
of XLPE designated tree retardant (TRXLPE) has replaced the use of XLPE for
medium-voltage applications. High-voltage transmission cables still utilize
XLPE, but they usually have a moisture barrier. TRXLPE is a very low loss dielectric
that is reasonably flexible and has an operating temperature limit of 90°C
or 105°C depending on type. TRXLPE because it’s cross-linked, does not melt
at high operating temperatures but softens. EPR is a rubber-based insulation
having higher losses than TRXLPE and is very flexible and has an operating
temperature limit of 105°C. EPR does not melt or soften as much as TRXLPE at
high operating temperatures, because of its high filler content.
4. The insulation shield-A semiconducting layer to provide a smooth cylinder
around the out side surface of the insulation. Typical shield compound is a
polymer with a carbon filler that is extruded directly over the insulation.
This layer, for medium-voltage applications, is not fully bonded to the insulation
(strippable) to allow relatively easy removal for the installation of cable
accessories. Transmission cables have this layer bonded to the insulation,
which requires shaving tools to remove.
5. The metallic shield-A metallic layer, which may be composed of wires, tapes,
or corrugated tube.
This shield is connected to the ground, which keeps the insulation shield
at ground potential and provides a return path for fault current. Medium-voltage
cables can utilize the metallic shield as the neutral return conductor if sized
accordingly. Typical metallic shield sizing criteria:
a. Equal in ampacity to the central conductor for one phase applications.
b. One-third the ampacity for three-phase applications.
c. Fault duty for three-phase feeders and transmission applications.
6. Overall jacket-A plastic layer applied over the metallic shield for physical
protection. This polymer layer may be extruded as a loose tube or directly
over the metallic shield (encapsulated).
Although both provide physical protection, the encapsulated jacket removes
the space present in a loose tube design, which may allow longitudinal water
migration. The typical compound used for jackets is linear low density polyethylene
(LLDPE), because of its ruggedness and relatively low water vapor transmission
rate. Jackets can be specified insulating (most common) or semiconducting (when
jointly buried and randomly laid with communication cables).
7. Moisture barrier-A sealed metallic barrier applied either over or under
the overall jacket.
Typically used for transmission cables, this barrier may be a sealed tape,
corrugated tube, or lead sheath.
Cable components 1-4 comprise the cable core, which in cross-section, is a
capacitor with the conductor shield and insulation shield making up the plates
on each side of a dielectric. These plates evenly distribute the electric field
radially in all directions within the insulation; however, until the metallic
shield is added and effectively grounded, the insulation shield is subject
to capacitive charging and presents a shock hazard. To be considered effectively
grounded, the National Electrical Safety Code (NESC) requires a minimum of
four ground connections per mile of line or eight grounds per mile when jointly
buried with communication cables for insulating jackets. Semiconducting jackets
are considered grounded when in contact with earth.
Because medium- and high-voltage cables are shielded, special methods are
required to connect them to devices or other cables. Since the insulation shield
is conductive and effectively grounded, it must be carefully removed a specific
distance from the conductor end, on the basis of the operating volt age. Once
the insulation shield has been removed, the electric field will no longer be
contained within the insulation and the highest electrical stress will be concentrated
at the end of the insulation shield ( FIG. 4). Premolded, cold or heat shrink,
or special tapes are applied at this location to control this stress, allowing
the cable to be connected to various devices ( FIG. 5).
===
Insulation Conductor
Percent of conductor voltage Semiconducting cable shield Semiconducting strand
shield Conductor Insulation

Above: Fig. 4 Voltage distribution in the insulation with the cable shield
removed.
===
Cable splice Cable elbow termination Cable outdoor termination

Above: Fig.
5 Cable accessories.
===

Above: Fig. 6 (A) Multigrounded shield, (B) single point grounded shield,
and (C) cross-bonding shields.
====
5 Shield Bonding Practice
Generally, the metallic shields on distribution circuits are grounded at every
device. Transmission circuits, however, may use one of the following configurations.
Multiple ground connections (multigrounded) ( FIG. 6A): The metallic shield
will carry an induced current because they surround the alternating current
in the central conductor. This circulating current results in an I^2 R heating
loss, which adversely affects the ampacity of the cable.
Single point grounded ( FIG. 6B): The metallic shield is grounded at a single
point and no current can flow in the metallic shield because there is no closed
circuit. This configuration allows the maxi mum ampacity rating for the cable;
however, a voltage will be present on the open end, which may be a hazard.
This voltage is dependent on the cable spacing, current, and cable length.
Cross-bonding ( FIG. 6C): The three-phase circuit is divided into three equal
segments. The metallic shield between each segment is connected to an adjacent
phase using insulated conductor.
Splices at these segments must interrupt the insulation shield to be effective.
6 Installation Practice
When cables are directly buried in earth, the trench bottom may require bedding
sand or select back fill free from rocks that could damage the cable over time.
When the cable is installed in conduit, the pulling tension must be limited
so as not to damage the conductor, insulation, or shields. Typical value when
using a wire basket grip is 3000 lbs. When the cable is pulled around a bend,
the pulling tension results in a side-wall bearing force against the inside
surface of the elbow. This force must be limited to avoid crushing the cable
components. Cables also have a minimum bending radius limit that prevents distortion
of the cable components.
7 System Protection Devices
Two types of protecting devices are used on cable systems.
1. Overcurrent-Fuses or circuit breakers. These devices isolate the cable
from its source, preventing the flow of damaging levels of current during an
overload, or remove a faulted cable from the system allowing restoration of
the unfaulted parts.
2. Overvoltage-Surge arrester. This device prevents damaging overvoltages
caused by lightning or switching surges from entering the cable by clamping
the voltage to a level tolerated by the cable insulation.
8 Common Calculations Used with Cable
- Inductance
- Inductive reactance
- Capacitance
- Charging current
- Ampacity
- Voltage drop
|