1. Introduction
As the demand for, and societal dependence upon, electricity has grown,
so too have the complexities of maintaining ever-growing transmission and
distribution systems. From its inception in the late 1800s to today, the
electric grid has undergone a significant growth, both in its geographic
reach and transfer capability.
With this increasing demand came the need of longer distances for that
electricity to be transmitted, due to the siting of large power-generating
facilities away from major load centers. This required the development
of higher voltages and ampacities, achieved through technological advances
in the field of electric power transmission equipment, construction, and
design. Longer transmission line distances were also driven by the interconnection
of neighboring utility systems, which provided the key benefit of reliability
through reserve sharing.
All of this, over time, has led to a change in the concept or definition
of "transmission." Voltages, which might have once been considered "transmission" level
are now commonplace for local distribution and subtransmission systems.
Today, typical extra high voltage (EHV) transmission line voltages in
the United States are 765, 500, and 345 kV. Other common voltage classes
utilized as transmission are 230, 161, 138, 115, and 69 kV. Many utilities
differ in their definitions of what transmission is defined as. Per FERC
Order 743, the bulk electric system has been defined as "greater than
100 kV"; thus, many entities will now use that definition for transmission.
Some companies also use the term "subtransmission" as an intermediate
level between distribution and transmission. In the western United States,
500, 345, and 230 kV make up the larger inter connection backbone, whereas
69-161 kV are typical voltage levels for local-area transmission systems.
In general, transmission line reliability is a greater concern than for
distribution lines, since transmission substations typically serve as the
source for delivering power to the subtransmission and/or distribution
system from a variety of resources. Also, as mentioned previously, transmission
typically connects multiple utility systems together, allowing for a more
efficient, cost-effective, and reliable system. Along with this is also
the fact that greater amounts of power, and thus customers, are at risk
for every trans mission outage or contingency. The existing NERC Transmission
Planning (TPL) standards reflect this concept, as it does not allow for
the loss of load when a single transmission element encounters an outage.
However, the NERC standards are not the initiating force behind the need
to study outage performance. Transmission reliability concerns have been
integral to power system planning since the inception of the lines themselves.
Factors such as design, weather performance, common mode outages, and outage
performance of lines are key facets of the overall design and specification
of electrical systems.
Empirical data gathering and analysis are a necessary component of ensuring
ongoing reliability and safety of systems. Engineers inherently seek to
have a rule-of-thumb for a variety of issues; compiling outage data over
time aids that continuous effort, helping to learn from mistakes and institute
improvements over time.
2. Common Terminology for Analyzing
Transmission Outage Data
One of the key issues when discussing data of any sort is the adherence
to a specific set of definitions which is commonly understood. In the electric
power industry, the majority of statistical/probabilistic analysis is focused
on distribution system related outages. However, IEEE Standard 8591 has
definitions for power transmission. This standard was recently reaffirmed
in 2008. Some of the basic definitions and how they are calculated are
included hereafter.
In-service state: The component or unit is energized and fully connected
to the system.
Outage state: The component or unit is not in the in-service state; that
is, it is partially or fully isolated from the system.
Reporting period time: The duration of the reporting period (equals service
time plus outage time).
Service time: The accumulated time one or more components or units are
in the in-service state during the reporting period.
Outage time: The accumulated time one or more components or units are
in the outage state during the reporting period.
Outage duration: The period from the initiation of an outage occurrence
until the component or unit is returned to the in-service state.
Outage rate: The number of outage occurrences per unit of service time
= # of outage occurrences/ service time.
Availability = Service time/reporting period time.
Unavailability = Outage time/reporting period time.
3. Transmission Outage Data Sources and Current Data Gathering Efforts
The following list identifies transmission outage data gathering efforts
throughout North America:
ECAR, the former regional reliability organization known as East Central
Area Reliability, had a continuous data collection until after the 2004
data collection. ECAR gathered automatic and nonautomatic outage data.
This data collection was halted in anticipation of the NERC TADS efforts.
The Canadian Electric Association or CEA has been gathering transmission
circuit and transformer outage information since 1978. Canadian Electric
Association gathers outage data for transmission lines but also for transformers,
circuit breakers, cables, shunt reactors and capacitors, series capacitors,
and static and synchronous compensators. The outage reports are available
if a member of the CEA.
The MAPP, Mid-Continent Area Power Pool, did data collection in the 1970s
and 1980s and helped in the development of common definitions and measures.
The WECC TRD, Western Electricity Coordinating Council, Transmission Reliability
Database, development began with data collection in 2006. The WECC TRD
data gathering is active and will be further explained in the next sections.
The NERC TADS, North American Electricity Corporation, Transmission Availability
Database System, first year of data collection was 2008. The NERC TADS
data gathering is active and will be further explained in the next sections
FIG. 1.
4. Western Electricity Coordinating
Council: Transmission Reliability Database
The WECC TRD was developed as a result of the PBRC, probabilistic-based
reliability criteria-development in the late 1990s and creation of the
workgroup called the RPEWG-reliability performance evaluation work group.
Data gathered for the WECC TRD are automatic outages for transmission
elements greater than 200 kV. The data for nonautomatic/manual outages
are not gathered, as these outages were deemed within WECC as having no
benefit.
FIG. 1 NERC regions.
The members of WECC wanted to incorporate probabilistic planning into
the WECC planning criteria and process instead of simply just deterministic
methods. Because of this approach, the PBRC was developed to define the
limits and expectations of outage frequency. From this process, outage
frequency rates were developed for the NERC Table I outage categories.
This is for the contingency Categories of A, B, C, and D. Based on these
outage frequency rates; transmission facilities within WECC were then expected
to perform at that rate for the outage category.
Within WECC, there has been a long-enduring criterion for two transmission
circuits in a common corridor. This criterion within WECC states that for
two circuits within the stated definition of a common corridor that these
two circuits are to be held to the NERC Category C performance requirements
as well as more stringent WECC requirements. This is to be considered a
Category C contingency.
Because this common corridor criterion is more stringent than NERC standard
performance requirements, there was a process developed within WECC to
allow for an exemption for two corridor circuits from the more stringent
requirements that met certain requirements for the exemption. This exemption
process is called the PCUR or performance category upgrade request.
There are two main aspects of a PCUR; the first being robust line design
or proving that the design of the potentially exempted line is more robust
per certain criteria listed in the documents accompanying the robust line
design process, and the second by showing proof that the circuits in the
corridor will or do have an expected outage rate that is more reliable
than the outage rate listed in the WECC criteria for this contingency.
Therefore, the two circuits in the common corridor need to show outage
MTBF greater than the listed rate of 0.033-0.33. The transmission owner
that is requesting the PCUR needs to show that the outage frequency is
greater than one in 30 years.
The TRD was developed to assist this process in two ways. The first to
develop a database that potential PCUR transmission owners will have a
database developed that can be used for typical or similar corridor outage
rates for newly constructed or planned corridors. The second reason is
to give the RPEWG the data it needs to follow or track the performance
of existing corridors to monitor the performance relative to the outage
rate. Also, to have a performance track of those exempted corridors, to
ensure they are performing to expected values.
The assignment of developing the TRD began in the early 2000s, and the
work on development of the database began in early 2004 and
was formally accepted by the WECC in 2006. The data submittal of 2006 was
the first year of TRD data submittal. As of this writing, there have been
four TRD annual reports with data analyzed each year more and more to try
and get to more meaningful results from the data submittal (TABLE 1).
The following tables are compiled from data listed in the WECC TRD report.
The current or latest year's data is listed as well as the average of the
past four submittals.
The focus of the outage statistics in the TRD reports:
WECC transmission totals, momentary outage summary, sustained outage summary,
outages per month, sustained transformer outage rate, transformer age summary,
outage rate per bank by trans former age, outage rate of common corridor
and common tower, outage rate per each physical attribute, voltage level
outage cause code.
The focus of the TRD is to gather data of elements >200 kV and to focus
on the physical design aspects of transmission circuits and transformers.
This focus will allow a cooperation or coordination of all WECC members
if particular equipment is seen to be failing at one TO or subregion and
to give warning to other part of WECC of these failures. Each year outage
rates are calculated for the number of overhead ground wires, conductors
per phase, type of insulator, structure material, structure type, water
rain type, elevation range. These results are shared in the WECC TRD report
each year. Each year the RPEWG is developing different techniques to allow
the witness of a systemic problem to convey to all of WECC.
The WECC TRD is a voluntary data submittal. But in 2009, 100% of WECC
TOs submitted their data.
This is due to the NERC TADS which is a mandatory data submittal and the
WECC has designed the TRD data submittal to cover both data submittals
of the WECC TRD and NERC TADS.

TABLE 1 WECC Disturban-Performance Table of Allow Able Effects on Other
Systems

TABLE 2 2009 WECC TRD Data

TABLE 3 2009 WECC Momentary Outages

TABLE 4 2009 WECC Sustained Outages
From TABLE 2, we see that WECC is predominantly a 230 and 500 kV system
with 1500-1600 outages per year across the entire WECC system.
In TABLE 3, the momentary outages are calculated for the WECC system and
compared to the trailing year's data shown as average values. The values
show that the system indices improved in 2009.
TABLE 4 shows the sustained outage rates for the WECC system. The values
show that the system indices improved in 2009 versus the average values.
5. North American Electricity Reliability Corporation: Transmission
Availability Database System
NERC TADS was started on the premise that transmission availability data
will help to quantify NERC transmission system performance and reliability.
NERC has taken the role of being an independent source of reliability performance
information, a recommendation of the April 2004 United States- Canada power
system outage task force report on the August 14, 2003 Blackout. The TADS
task force was initiated in October 2006 to write the approach for transmission
outage data reporting and measuring availability and performance. This
became the NERC TADS.
NERC TADS collects outage data on specific lines while supplying utility
aggregate transmission population information. NERC TADS will be implemented
in two phases: Phase I is the collection of automatic outages began with
the year 2008 data, Phase II adds the requirement of supplying the automatic
outages as well as the nonautomatic outages for the calendar year. The
first year of the nonautomatic outage data collection will be for the data
collection of calendar year 2010.
The focus of the reporting in the TADS Reports:
There are a total of nine reports; there are NERC-wide and eight regional
reports for each of the regions listing summary of NERC-wide results, all
AC circuit metrics, all DC circuit metrics, all transformer metrics, and
AC/DC back-to-back converter metrics.
The data structure for TADS will gather aggregate transmission population
from the TOs while gathering specific data for each outage.
The purpose of TADS is to provide outage cause analysis and outage Event
analysis. Event analysis will aid the in the determination of credible
contingencies and will results in better understanding, and this understanding
should be used to improve planning and operations.
In addition, trending each Regional Entity's performance against its own
history will show that region's performance is changing over time. Given
the vast physical differences between regions and TOs (weather, load density,
geography, growth rate, system age, customer mix, impact of significant
events, average circuit mileage, etc.), we believe that comparisons for
the purposes of identifying relative performance between regions are not
appropriate. Taken from the NERC TADS revised final report, September 26,
2007.
5.1 Data in Annual Reports
The data listed in Tables 5 and 6 shows the results for all of NERC
for 2009. The numbers for the columns are total circuit outage
frequency (TCOF), sustained circuit outage frequency (SCOF),
and momentary circuit outage frequency (MCOF). More information can be
found at www.nerc.com.

TABLE 5 2009 NERC Wide Outage Summary

TABLE 6 NERC 2009 Outage Totals
6. Salt River Project Transmission Outage Data
What is Salt River Project (SRP)? SRP is a municipal electric power and
water utility that serves the Phoenix, AZ metropolitan area.
The SRP system has
Line Parameters-Mileage, Rating, and Other Data 500 kV (Overhead pole
miles) 357 230 kV (Overhead pole miles) 411 115 kV (Overhead pole miles)
264 69 kV (Overhead pole miles) 903 69 kV (Underground miles) 8
The SRP bulk transmission and subtransmission system consist of facilities
and electrical equipment in the 500, 230, 115, and 69 kV voltage classes.
6.1 SRP Operating Environment
In order to reliably serve its customer load, SRP addresses specific design
challenges associated with its operating environment. For example, temperatures
in the Phoenix metro area can range from 20°F to 122°F. Due to high cooling
needs, SRP's system peak load occurs annually during the summer after several
hot days in a row with temperatures above 115°F. In order to address the
extreme weather operating conditions, SRP designs its transmission in a
manner that prevents thermal overloading of equipment during peak demand
periods. Therefore, SRP's transmission system is highly reliable due to
the development of an overall system design architecture, equipment specification,
maintenance, and planning and operational standards. In order to present
evidence that SRP's transmission system designs, operating and maintenance
practices are adequate to meet the environmental demands, SRP measures
its trans mission reliability performance by collecting and analyzing transmission
disturbance event data.
6.2 Transmission Event Data Capture
A transmission event or disturbance is defined as an abnormal system condition
that may include electric system faults, equipment outages, frequency deviations,
voltage sags, etc. Because SRP captures the data in the context of the
event, the data quality is excellent and operations personnel are made
aware of system events that may influence current and near-term system
operations.
6.3 Transmission Event Data Characteristics
Transmission event data can be broadly classified into two distinct categories.
One is a set of "random" events that represent environmental
impacts regardless of the system design, maintenance, and operations. These
random events contribute approximately 75% of the total annual transmission
event count.
The other category is classified as "nonrandom" events and is
directly related to the system design, maintenance, and operation practices.
Annual event counts of transmission system are very low com pared to distribution
system event counts. Current reliability reporting practices comingle random
and nonrandom events in such a manner to often provide management with
misleading information.
6.4 Nonrandom Event Performance Analysis of Actionable
Transmission System Events
NREP represents a new reliability reporting and analysis concept that
seeks to separate actionable information from random transmission event
data. The underlying aspect of NREP is that electric utilities design their
systems to perform in the environment in which they are expected to operate.
NREP analysis differentiates transmission event data that reflects the
fidelity of a transmission design, maintenance, and operating practices
to the data that does not.
6.5 Potential Uses of the Nonrandom Event Performance, NREP, Feedback
Each utility uses a list of outage cause codes that the outages of the
system are charged into for collection and, if necessary, more intense
data scrutiny. SRP uses the following outage cause codes in that all 69
kV through 500 kV outage will be categorized.
6.6 Category Random
Animals, vehicle caused, bird contact, contamination, customer caused,
debris in equipment, environ mental condition, fire, foreign system, unknown
with fault, inadvertent by public, lightning, rain, storm with unknown
cause, unknown with no fault, vandalism, and wind.

FIG. 2 The SRP system NREP.
6.7 Category Nonrandom
AC circuit equipment, breaker failure, communications, control, relay,
EMS failure, inadvertent by SRP, unmitigated distribution fault, under-built
line, shunt capacitor or reactor failure, power system condition, pole
failure, series capacitor failure, AC substation equipment failure, vegetation
or transformer failure.
There are three things that can be done from the feedback, do nothing,
change maintenance spending, or change design. The feedback from NREP can
give a better idea of how to proceed, if desired.
If the system shows a downward trending NREP, then the maintenance dollars
could be potentially decreased to save money and to allow the NREP to raise
enough to be within acceptable limits. How to define the acceptable limits?
If the system shows an upward trending NREP, then the time for maintenance
spending increases is now or soon depending on how close to acceptable
limits.
Maintenance spending is a quicker feedback mechanism for the NREP because
design changes may take many, many years to see the influence because the
existing system is very large given that the design changes will have impact
over time as system is added.
In FIG. 2, the SRP system NREP is shown for the past 6 years. The vertical
bars represent all outages and the horizontal lines are the NREP values.
The NREP value is shown to be decreasing.
Also, only a small percentage of the total customer outages are transmission
caused but there is always the possibility of transmission outage cascading,
leading to multiple outages that may cause large scale customer outages
or system-wide outages. Therefore, transmission outages may not be a great
influence on customer outages normally, but the possibility always exists
for this to turn large scale and regional.
Transmission outage data can serve the utility in the following ways:
1. Demonstrating the design, maintenance, and operational practices that
meet or exceed the challenges posed by the environment
2. If the practices need to be changed to increase reliability
3. If improvements are needed operationally
Typically, SRP experiences four to six 69 kV line outages each year caused
by an inadvertent action by SRP personnel. In 2008, SRP experienced 16
of these outages. There were two main causes that can be attributed to
the increase. In 2008, relay maintenance revised their maintenance practices
to include exercising inputs and outputs on relays. Also, at this time,
three times the normal number of relays was upgraded in the first half
of the year that contributed to this high number of outages. These practices
were changed after 6 months and the outage rates returned to normal. The
number of inadvertently caused outages returned to a typical value, 2 total,
in 2009.
The number of transmission initiated outages versus the number of distribution
caused customer outages:
2009 38/7343 = 0.5%
2008 86/8152 = 1.05%
2007 85/7908 = 1.08%
2006 114/7763
= 1.46%
2005 54/8133 = 0.66%
6.8 NREP Conclusion Section
NREP transmission event data analysis conveys the system's reliability
of how well the system reacts to its environment. NREP provides an easily
understood model to demonstrate to the stakeholders whether the system
is performing adequately or not. Additionally, NREP analysis can provide
a frame work that enables a true utility to utility reliability performance
comparison.
7. Southern California Edison Transmission Outage Data
Southern California Edison (SCE) is one of the largest electric utilities
in the United States, providing electric service to nearly 14 million people
throughout a 50,000 square mile service territory. The service territory
is quite diverse geographically, exposing it to a variety of different
climates. SCE has been gathering transmission outage data for 50-plus years.
A summary of SCE's transmission and subtransmission line mileages as of
2010 is provided hereafter.
Line Mileages (approx)
500 kV (Overhead lines) 1031
230 kV (Overhead lines) 3379
230 kV (Underground
lines) 1
115 kV (Overhead lines) 1874
115 kV (Underground lines) 16
66
kV (Overhead lines) 4838
66 kV (Underground lines) 254
SCE's system design philosophy differs in two key ways from other utilities.
First, SCE utilizes a radial design. All loads at any "A-station" (see
squares in the following diagram) serve load on lower voltages (i.e., subtransmission
systems) radially, meaning the lower voltage levels (i.e., 66 and 115 kV)
are not net worked to other transmission stations during normal operation.
Another way to think of this is that the subtransmission system is not
operated electrically parallel to the transmission system. SCE is a participating
transmission owner within the California Independent System Operator (CAISO),
and thus the CAISO has operational control of the SCE transmission system.
The majority of subtransmission and distribution systems SCE owns are still
under the operational control of SCE. SCE follows this design philosophy
since the original system development. This is due to the simplicity it
brings in operating, planning, and designing subtransmission systems. Second,
SCE is a large importer of electricity from outside the service territory,
significantly depending on the EHV transmission system to import energy
throughout the western United States ( FIG. 3).
Due to this slightly different philosophy and being a large importer of
power with a vast and geo graphically diverse service territory, SCE requires
a higher level of reliability from its transmission system. Rather than
solely looking at the aggregate statistics, SCE's planning engineers focus
their attention on ascertaining which outages are more frequent(or credible),
by annually evaluating the outage data. This is in addition to availability
reports and other regulatory obligations that SCE submits data to NERC,
WECC, CAISO, and the state of California.
SCE Number of transmission circuit initiated customer outages versus the
number of distribution circuit initiated customer outages:
2010 2/15,900 = 0.01% 2009 1/14,042 = 0.01% 2008 12/14,780 = 0.08% 2007
0/15,801 = 0.00% 2006 0/17,580 = 0.00%
SCE experiences a significant amount of 500 kV outages every year due
to wildfires. As this is a common occurrence throughout its service territory
annually, SCE criteria specify a separation of a third EHV circuit from
any other two circuits within the same right-of-way. These criteria were
developed due to the historical experience SCE had in the development of
the Pacific AC Intertie lines.

FIG. 3 Typical SCE electric system voltage classes.
Due to SCE's dependence on the EHV system, it is essential not to put
more than two EHV circuits in corridors exposed to extreme conditions,
such as fire. Allowing a separation of 2000 ft or more between circuits
can address this issue. These criteria serve as an example of how long-term
data gathering efforts can guide utilities in prudently planning for the
nuances of their unique service territories.
8. Conclusion
While there is a significant amount of work that has been performed regarding
transmission outage data, the authors foresee that this work will only
increase in the future, due to the even greater importance of reliability
on transmission systems. The computational abilities of today, compared
to that of a few decades ago, will allow for even more variations of data
analysis and interpretation.
By the use of outage data over time and the vigilant investigation of
outages and properly written out age cause codes can lead to potential
feedback to the power system design and potential changes to the design
over time. There may be potential feedback to maintenance practices as
well.
Through experience, one can glean that the statistics and probabilities
alone will not tell the whole story; specific details on certain lines
can typically be an important piece of the puzzle during event analysis.
However, in order to evaluate any large sample of data, it is understood
that one must use the methods used in the examples mentioned earlier in
the section. However, the authors urge readers to be cognizant of the fact
that data can be presented in ways that could mislead; thus, it is always
beneficial to obtain more specific information when making significant
decisions.
The authors would like to thank all those involved in the compilation
of this section, specifically those at both SCE and SRP, and their families. |