An overhead transmission line (OHTL) is a complex electric/mechanical system
designed to transfer electricity between power substations. Structural elements
must safely and reliably support current carrying conductors while providing
the necessary separation between individual line phases and the ground. Transmission
lines are composed of many individual elements consisting of a variety of materials
with a wide range of mechanical properties. The difference in performance of
these components is evident in their mechanical characteristics, such as the
following:
• Flexible vs. rigid
• Ductile vs. brittle
• Variant dispersions of strength
• Wear and deterioration occurring at different rates
Transmission lines consist of two separate structure systems: the structural
support system comprised of towers/poles and foundations, and the wire
system comprised of conductor, shield wire, insulators, and hardware. The
structural support system is required to provide support for the wire system
while accommodating ice and wind acting on both the structural support
system and the wire system.
This discussion addresses the types of design practices normally required
for the structural support system.
1. Transmission Line Design Practice
Traditional and modern transmission line design follows several common
practices. These include providing overhead conductor and shield (ground)
wire configurations that meet minimum clearance requirements based on the
voltage level of the line as required by the National Electrical Safety
Code (NESC) (IEEE, 2006), as well as other applicable codes. The NESC and
similar codes provide specified requirements for the separation of the
following:
• Energized parts from other energized parts
• Energized parts from the support structure and other objects located
along the right-of-way
• Energized parts aboveground
Transmission line loads can be classified as weather-related, accidental,
or caused by construction or maintenance activities. Analysis of weather-related
events is typically governed by national or regional codes (such as NESC),
while accidental, construction, and maintenance events are primarily developed
by utilities for the specific needs and conditions of their service territory,
with many based on commonly accepted practices. Traditional design includes
some probabilistic evaluations of weather-related events but relies mostly
on a deterministic process from successful experience. Load cases for accidental
events such as component breakage, wear or fatigue, structure failure from
natural disasters or terrorism, and other unforeseen events are analyzed
to provide designs that minimize their consequences to the OHTL as a whole
and prevent an uncontrolled cascade-type system loss. These cases are considered
special security requirements. Evaluations for safety requirements are
applied to more predictable operational, construction, and maintenance
events where calculated loads are analyzed using both regulations and standard
codes of practice.
OHTLs are suspended and spaced to produce code-required conductor and
shield wire clearances.
Resultant structure loads are influenced by not only the sag/tensions
but also variable meteorological conditions that act in both transverse
and longitudinal directions. NESC provides requirements to evaluate these
conditions that include combined ice and wind loading criteria divided
into three distinct loading districts: heavy, medium, and light. Each district
defines regional climate variations with different combinations of radial
ice thickness, wind pressure, and ambient temperature. NESC requirements
also give extreme wind loading, providing basic wind speeds that must be
adjusted (with consideration for height and gust response) separately for
both the wire and the support structure systems. The final NESC load criterion
that must be considered is extreme ice with concurrent wind. The NESC provides
loading maps for each of these requirements.
In recent years, NESC has adopted reliability-based design (RBD) using
the load resistance factor design (LRFD) approach and now includes load
factors and strength factors. Load factors consider the uncertainty of
the load event, the possibility the design loads will be exceeded, the
grade of construction, and structure function. Load factors, though, do
not consider the type of material. Strength factors at installation are
provided by NESC and take into consideration the type of material and deterioration
characteristics.
The design of a transmission line normally includes the following steps:
1. The utility prepares an agenda of loading events consisting of
a. Mandatory regulations from the NESC and other codes
b. Climatic events assumed representative of the line's specific location
c. Contingency (security) loading events of interest, i.e., broken conductor
d. Safety requirements and expectations, i.e., maintenance loads, stringing,
etc.
Each of these loading events includes load factors to cover associated
uncertainties to produce a set of factored design loads.
2. A ruling span is identified based on the sag/tension requirements
for the preselected conductor.
3. Structure type is selected based on past experience, utility standards,
recommendations of potential structure suppliers, terrain and construction
issues, economics, and long-term maintenance concerns.
4. Ultimate design loads resulting from the ruling span are applied statically
on components in the longitudinal, transverse, and vertical directions,
and the structure is either designed by deterministic or reliability-based
methods.
5. Using the loads and structure configuration, ground line reactions
are calculated and used to complete the foundation design. Foundations
are also designed using either deterministic or RBD methods.
6. The ruling span line configuration is adjusted to fit the actual right-of-way
profile.
7. Structure/foundation designs are modified to account for variation
in actual span lengths, changes in elevation, and running angles.
Traditional line design views the support structure as an isolated element
supporting half span of over head conductors and shield wires on either
side of the structure. Using ruling span assumptions with similar span
lengths and suspension supports in the tension section yields somewhat
accurate results.
Ruling span assumptions become less accurate in conditions where span
lengths vary in hilly terrain.
Under these conditions, sag differences can be much different from the
ruling span assumptions. It should also be noted that inaccuracies when
using ruling span assumptions under high temperature, unbalanced ice, and
broken wire conditions are also evident. Thus, modern line design practice
using computer-based programs enables a more accurate development of loads
at each structure location, clearance to ground, and clearance to structure.
Inasmuch as structure types are available in a wide variety of configurations,
materials, and costs, several iterations would normally be attempted in
search of the most cost-effective line design based on total installed
costs.
While traditional deterministic design using static loads is a convenient
mathematical approach, it is obviously not representative of the real-world
exposure of the structural support system. OHTLs are tens of yards wide
and miles long and usually extend over many widely variant topographical
and climatic zones, each capable of delivering unique events consisting
of magnitude of load at a probability of occurrence. That component along
the right-of-way that has the highest probability of occurrence of failure
from a loading event becomes the weak link in the structure design and
establishes the reliability level for the total line section. Since different
components are made from different materials that have different response
characteristics and that wear, age, and deteriorate at different rates,
it is to be expected that the weak link
• Will likely be different in different line designs
• Will likely be different in different site locations within the same
line
• Can change from one component to another over time
1.1 Transmission Line Support Structures
Structures used for transmission lines come in a wide range of materials,
shapes, and configurations.
Typical materials and shapes include but are not limited to the following:
• Steel (hot-rolled angles, plates, formed plate polygonal tubular members)
• Aluminum (extruded shapes, plates)
• Concrete (static cast, spun cast with pre- or post-tension strands)
• Wood (glue-laminated poles and crossarms, poles, crossarms)
• Fiber-reinforced polymer (FRP) (crossarms, poles) There are a variety
of configurations used for transmission structures. These include the following:
• Lattice towers (steel, aluminum) (ASCE, 2000)
• Single shaft poles (steel, wood, FRP, concrete) (IEEE, 1991; ASCE, 2003;
Magee, 2006)
• H-frame structures (steel [latticed and tubular], wood)
• Guyed structures (steel [latticed and tubular], concrete) (ASCE, 1997)
• Framed structures (tubular)
Utility standards, operational and maintenance procedures, installed cost,
lifetime cost, structure performance, right-of-way access and terrain,
and aesthetics are just some of the issues that must be considered when
selecting a structure type for a transmission line. Long-term considerations
for future upgrades may also impact final selection of material and structure
configuration.
1.2 Transmission Line Foundations
The function of a transmission foundation is to transfer applied steady-state
and transient loads into the surrounding soil and rock while limiting structure
movement. Loads are conveyed to the subsurface at the ground line interface,
where either a separate foundation system is installed and connected to
the structure or the above-grade structure is directly buried and backfilled.
Foundation systems can be categorized in the following general groups:
• Spread foundations (steel grillages and reinforced concrete)
• Reinforced concrete drilled shafts
• Direct embedment poles (steel, wood, concrete)
• Driven piles (steel, wood, concrete)
• Anchors (various materials and configurations)
Detailed descriptions of transmission foundation systems are provided
by the Institute of Electrical and Electronics Engineers (IEEE) Standards
691 and 977 (IEEE, 2001, 2010).
Spread foundations typically support lattice tower structures using either
a reinforced concrete or a prefabricated steel grillage footing for each
leg. Guyed lattice structures use a combined system of one or more spread
footings in conjunction with guy anchors.
Because of their ability to resist uplift loads, compression loads, and
lateral overturning forces, drilled shaft foundations are used to support
a wide variety of transmission system structures, including lattice towers,
single shaft steel poles, and framed pole structures. Drilled shafts are
connected to lattice towers typically with bent or angled structural steel
angles embedded into the reinforced concrete foundation. Most often, single
pole and framed pole structures (and occasionally lattice
towers) include steel base plates at the bottom of the structure which
are fixed to the foundation via steel anchor bolts in either a circular
or rectangular pattern around the inside perimeter of the shaft.
These anchor bolts can be partially or fully extended within the drilled
shaft and can be made part of the reinforcement cage or be contained within
and separate from reinforcement. Drilled shaft foundations are typically
uniformly cylindrical but can be drilled with tapers, uniformly variable
shaft sections, or belled bottoms.
Lower voltage lines with lighter loading conditions can be supported with
single pole or frame pole structures directly embedded within a drilled
shaft hole, then backfilled with a variety of natural and man-made materials.
The annulus space around the pole can be filled with concrete, compacted
native soil, or slurried aggregates either with or without cement. Permanent
steel casing is sometimes incorporated with direct embedment foundations
where groundwater is present.
Piles (or more commonly piles in closely spaced groups) are either mechanically
driven or vibrated into the ground to support all types of transmission
structures. Generally this is done where ground conditions are soft enough
to accept the concrete, steel, or wood piles. Structures are fixed to pile
groups often with cast-in-place reinforced concrete caps. Lightly loaded
wood poles can be fixed to single steel or concrete piles via mechanical
connection.
Foundation anchors for transmission structures encompass a large variety
of types and materials and are used to directly support guyed structures
or are encased within concrete-filled sockets with bottom anchor segments
embedded into subsurface rock to support single shaft poles. Guyed helical
anchorages are directly screwed into the ground; plated anchors are buried
in angled trenches then backfilled; and grouted anchors are placed in predrilled
holes then grouted to fill the surrounding space with high strength cement
or resin.
1.3 Factors Influencing Structure and Foundation Selection
There are a number of factors that can impact the selection of the structure
and foundation type used in a transmission line. In some cases, the foundation
requirements may dictate the structure selection; in others, it may dictate
the structure that is critical. Some of the more significant issues are
briefly identified in the following text.
Wire orientation: Flat, vertical, delta, single, or multicircuit configurations
will all influence selection of structure type.
Right-of-way: Width of the right-of-way, blow out concerns, adjacent lines
in the same right-of-way and terrain, all will influence structure selection
and configuration.
Erection requirements: Clearly different structure types require different
erection requirements. Latticed structures require an assembly yard or
a flat area on the right-of-way to lie out and assemble the sections of
the structure. Tapered steel poles require less assembly area but normally
need a larger crane for installation of the structure. This may involve
more extensive road work for crane access. Concrete poles require yet larger
cranes (and often mats) for support when lifting the structure. As expected
cost of assembly, erection, and installation of the foundations, all must
be considered in developing a total installed cost.
Public concerns: Probably the most difficult factors to deal with arise
as a result of the concerns of the general public living, working, or coming
in proximity to the line. It is common practice to hold public hearings
as part of the approval process for a new line. Such public hearings offer
a platform for neighbors to express concerns about structure appearance
and location that generally must be satisfactorily addressed before the
required permit will be issued.
Often the public perceives transmission structures as "eyesores" and
distractions in the local landscape. However, with the advent of sophisticated
software packages, line models using different structure types and configurations
can be used at public hearings. In some cases, these new tools have been
helpful in mitigating public concerns. Other concerns include electromagnetic
field effects (EMF) from the line, possible climbing access to the structures
by the public and audible noise.
Inspection, assessment, and maintenance: During the design process, it
is valuable to interact with line maintenance and inspection groups. Input
from these specialists will provide not only a positive relationship but
will also reduce the chance of fabrication or field changes to meet climbing
requirements.
Oftentimes, the owner's inspection and maintenance practices will influence
the selection of the structure type for use in a specific line location.
Inspections and assessment are normally made by humans who use diagnostic
technologies to augment their personal observations. Inspectors must work
from the most advantageous location when making inspections, and this can
require climbing the structure.
Methods can include observations from ground, fly-by patrol, climbing,
bucket trucks, or helicopters.
Likewise, there are certain maintenance activities that are required for
particular structure types. The equipment necessary to maintain the structure
should be taken into consideration during the structure type selection
process to assure there will be no unexpected conflict between maintenance
needs and right-of-way restrictions.
Future upgrading or uprating: Due to the difficulty of procuring rights-of-way
and obtaining the necessary permits to build new lines, some utilities
may select structure types for current line projects that more easily permit
future upgrading and/or uprating initiatives or may be designed with additional
capacity for future use.
Subsurface conditions: Site-specific ground conditions will control the
ease or difficulty in the construction of various transmission foundations.
Spread footings generally work best where shallow excavation is favored
over deep drilling. Drilled shafts must maintain their shape without caving
through the foundation construction process, so soils that are susceptible
to caving must either be cased or held open with specialized drilling fluids.
Alternately, stiff or strong soils and weak rock are ideal for drilled
shaft and direct embedment construction techniques. The subsurface variables
involved with foundation selection include site geology, soil/rock type,
soil strength properties, and groundwater conditions.
Access: Foundation type is sometime dictated by the ability to bring equipment
and material to the job site. Installation of drilled shafts or driven
piles requires track or truck-mounted rigs that typically need substantial
road access, while small spread footings and anchor systems can be carried
by hand or small all-terrain vehicles to more difficult locations. Long
distances to concrete ready-mix plants can increase the cost and possibly
reduce the quality of cast-in-place foundations such as concrete spread
footings and drilled shafts.

FIG. 1 Deterministic design approach.
2. Current Design Practices
2.1 Deterministic Design Approach
The deterministic design approach, often referred to as the allowable
stress design (ASD) approach, is shown schematically in FIG. 1.
The maximum component design load QD, shown in FIG. 1, is generally determined
from one of the following load cases:
• Extreme wind
• Extreme ice with concurrent wind
• Broken conductor and/or overhead ground wires
• Construction and maintenance
• Legislated loads
FIG. 2 exemplifies representative load cases for a typical steel lattice
tower where different members of the structure are controlled by different
load conditions.
===

FIG. 2 Typical steel lattice tower loading-load cases for structural
elements.
NESC heavy (ice and wind) One broken OHGW combined with wind and ice One
broken conductor bundle combined with wind and ice Heavy wind, no ice Wind
on bare tower (no conductors or OHGW) Vertical load at any conductor support
Vertical load at any OHGW support
===
Design load cases used in practice in North America are normally based
on the NESC (IEEE, 2006), American Society of Civil Engineers (ASCE) Manual
74 (Wong and Miller, 2010), and/or the Canadian Standards Association (CSA)
Standard C22.3 (CEI/IEC, 2006). The NESC divides the United States into
three large global loading zones-heavy, medium, and light-and specifies
radial ice thickness, wind pressure, and temperature relationships to define
the minimum load levels that must be used within each loading zone. In
addition, the NESC introduces the concept of safety factor in terms of
an overload capacity factor (OCF) to cover uncertainties stemming from
the following:
• Likelihood of occurrence of the specified load
• Dispersion of predicted strengths
• Grade of construction
• Deterioration of strength during service life
• Structure function (suspension, dead-end, angle)
Both ASCE Manual 74 and CSA Standard C22.3 include loads associated with
a 50 year RP as the basis of design.
Nominal component capacities (Rns) are based on using nominal material
strength and deformation properties as needed by the component element
design model being used by the designer. Component reliability is established
by using the following design equation:
[...]
QD is the maximum component design load Rn is the nominal capacity of
the component SF is the factor of safety
Above-grade structure component safety factors are typically established
in various design codes.
For foundations, the value of the safety factor adopted by the designer
is based on the background and experience of the designer. However, surveys
of the practice have shown that safety factors used in practice are quite
variable, resulting in a wide variation in the level of reliability and
cost for foundations.
2.2 Reliability-Based Design Approach
The RBD approach is founded on the assumption that component design loads
are not unique but can vary significant over the life of the component-from
relatively low loads (such as everyday wind events) to very high loads
(such as extreme wind events). Reliability level is defined as the ability
of a line (component) to perform its expected capability. In addition,
the nominal strength of each component can vary due to differences in as-built
material properties, dimensions, construction techniques, and design models.
Thus, in an RBD approach, the variability and uncertainty in loads and
component strengths are modeled by probability distribution as shown in
FIG. 3.

FIG. 3 Combined load and resistance probability distributions.
RBD applied to transmission line design is presented in detail by ASCE
and the International Council on Large Electric Systems (CIGRE SC-22, 1995).
Consideration of these uncertainties to achieve a low but acceptable probability
of failure is presented in the technical literature on structural reliability.
Reliability-based resistance factors, which separate the load (Q) and resistance
(R) density functions, are developed for each component element design
model so that failure will rarely occur. The probability of Q exceeding
R is the probability of failure and is determined by convolution of the
Q and R probability functions.
Using advanced first-order reliability methods demonstrated that if the
components of a transmission line system were designed for loads associated
with a specific time return period (RP) and component capacities have low
exclusion limits (e.g., 5%-10%), then the annual probability of failure
(Pf ) for these components is approximately equal to
½ ·?RP. For an RP of 50 years, Pf
equals ½ times 50, or a probability of failure of 0.01. In addition, Pf
was shown to be relatively unchanged with respect to the type and coefficient
of variations of the Q and R density functions. Thus, the RBD of transmission
line elements can be performed using the following equation:
R Effect of Dead Load Q 5 50 = + [ ] ?
( eqn. 2)
where
R5 is the 5% lower exclusion limit (LEL) capacity
? is the load factor used to modify line reliability for return periods
higher than 50 years Q50 is the 50 year return period design load event

TABLE 1 Approximate Load Factors to Convert "Extreme Wind Loads" from
a 50 Year Event to Other Return Periods-ASCE Manual 74
 TABLE 2 Approximate Load Factors to Convert "Extreme Ice with Concurrent
Wind Loads" from a 50 Year Event to Other Return Periods-ASCE Manual
74
 TABLE 3 Default Load Factors for Adjustment of Climatic Loads in Relation
to Return Period vs. 50 Year Event-CSA C22.3 No. 60826
Tables 1 through 3 provide load factor values (?) for extreme wind
loads, extreme ice and con current wind loads, and CSA C22.3 No. 60826
(CEI/IEC, 2006) loads, respectively.
The relationship between R5 and Rn is given by the following equation:
R R 5 5 n = F
(eqn .3) where
R5 and Rn are as defined previously F5 is the 5% LEL resistance (strength)
factor
Thus the RBD equation is given as follows:
(eqn. 4)
2.3 Security Level
It should be remembered, however, that the failure of every component
does not necessarily progress into extensive damage. A comparison of the
total risk that would result from the initial failure of components of
interest can be accomplished by making a security-level check of the line
design. Security level can be described as the ability of a line to restrict
progressive damage after the failure of the first component.
Since the OHTL is a contiguous mechanical system, the forces from the
overhead conductors and shield wires (wire system) on one side of each
tangent structure are balanced and restrained by those on the other side.
When a critical component in the wire system fails, energy stored within
tensioned elements is released suddenly and sets up unbalanced transients
that can cause failure of critical components at the next structure. This
can set off a cascading effect that will continue to travel down line until
encountering a point in the line strong enough to withstand the unbalance.
Unfortunately, a security check of the total line cannot be accomplished
from the information describing the single structure in FIG. 2, but perhaps
some generalized observations can be drawn for demonstration purposes.
A structure designed for broken conductor bundle and broken shield wire
contingencies would not appear to be subjected to a cascade from a broken
bare conductor. But what if the conductor was coated with ice at the time?
Since ice increases the energy trapped within the conductor prior to release,
it might be of interest to determine how much ice would be enough to overcome
the contingencies. Modern computer modeling would be employed to simulate
ice coating of increasing thickness until the critical amount is defined.
A proper micrometeorological study could then identify the probability
of occurrence of a storm system capable of delivering that amount of ice
at that specific location.
A security-level check can predict the amount of resulting losses and
damages that would be expected from an initiating event compared to the
other contingencies.
3. Foundation Design
Most often, foundation design is controlled by steady-state and transient
loads (one or a combination of both). Construction and maintenance loads
must be examined, but rarely influence foundation dimensions. Foundation
performance criteria (such as rotation and displacement) result from deterministic
evaluations of structure performance needs and can control final foundation
size. Failure is not necessarily a catastrophic event, but the point where
pre-established movement performance criteria are exceeded.
The IEEE/ASCE Transmission Structure Foundation Design Guide gives a thorough
presentation of transmission line foundation design. For either RBD or
traditional ASD, the steps involved with transmission line foundation design
remain the same:
• Perform subsurface investigation/obtain subsurface information
• Select subsurface foundation geotechnical design parameters
• Select appropriate foundation design model
• Apply loads to design model consistent with RBD or ASB
3.1 Subsurface Investigation
By virtue of their intended purpose, electrical transmission projects
traverse large distances across widely varying geologic and geotechnical
settings over many miles. Transmission foundation designers must balance
cost-effective field investigation with the production of sufficient data
for design of foundations that are economical and reliable. An initial
qualitative preliminary assessment of subsurface variation should be performed
by professionals skilled at geology or geologic engineering to optimize
and apportion investigation sites according to the geologic strata. This
process includes gathering of prior information in the form of soil reports,
geologic maps, aerial photographs, hydrologic reports, etc., combined with
new field observations and mapping. A field subsurface investigation based
on a thorough review of prior data follows and includes borings, test pits,
in situ probes, and geophysical measures. The purpose is to establish one
or more idealized profiles of the subsurface and gather samples for laboratory
testing.
3.2 Foundation Geotechnical Design Parameters
One of the most difficult aspects of transmission line foundation design
is the selection of representative soil/rock design properties for idealized
subsurface profiles at each foundation location. The process is generally
iterative: the properties are refined as more data are obtained from field
in situ work and laboratory testing. Quite commonly, index parameters from
standard penetration tests (SPT) and cone penetrometer tests (CPT) are
correlated to the design properties as these values tend to be abundant
from the investigations. Laboratory testing is used to refine the values
along with high-quality in situ methods such as pressure meter testing.
Empirical correlations to subsurface properties are extensively used for
estimating design parameters. Manuals and guides on this subject have been
prepared by the Electric Power Research Institute (EPRI) focusing on the
selection of geotechnical design parameters and investigation methods relative
to transmission lines. The selection of design parameters must always consider
the design model and approach. It is important to understand how models
apply soil properties to select reasonable low bound values for use in
traditional allowable strength design or to determine nominal values for
RBD.
3.3 Foundation Design Models
It is of great importance that the foundation designer selects a model
that accurately reflects subsurface conditions and reactions to the applied
loads. With the advent of modern computer analysis programs, there is a
tendency to use the software at hand and make the design fit the program.
Additionally, some utilities require specific models or software be used
in their specifications. In any case, the designer needs to fully evaluate
foundation models and understand the applications and limits.
Spread footings (cast-in-place concrete, precast concrete, grillages,
pressed plates) provide basic resistance to axial forces (uplift and compression),
while considering the load orientation (inclination and eccentricity) of
the applied loads. Foundations must be designed to prevent shear failure
and excess settlement in compression and have adequate size and depth to
prevent uplift failure or excessive lift of foundation legs. The IEEE/ASCE
foundation design guide offers a number of models for spread footings using
traditional design methods. AASHTO LRFD Bridge Design Specifications (AASHTO,
2010, Section 10.6) give detailed design methods for RBD of spread footings.
Spread footings are most commonly used with lattice tower structures and
as central bearing foundations for guyed lattice tower structures.
Drilled foundations (including reinforced concrete drilled shafts and
direct embedment poles) sup port vertical compressive loads through a combination
of side shear and end bearing, vertical uplift loads via side shear with
foundation weight, and lateral loads with overturning moments using the
lateral resistance of soil/rock within the embedded section. These foundations
rely on a complex soil-structure interaction where movement mobilizes soil
strength, transferring load in a nonuniform manner. With axial loads, this
commonly referred to as a "t-z" effect and with lateral loads,
a "p-delta" or "p-y" effect.
EPRI has developed software (FADTools) to model electric system drilled
shafts and direct embedment foundations. The lateral load program, MFAD,
accurately models the rigid nature of short electric sys tem shafts and
is calibrated for both traditional strength design and RBD.
Pile foundations transmit axial compressive loads through soft soils to
denser underlying soils or rock. Although pile foundations can provide
substantial uplift and lateral resistance, these foundations are most often
used for lattice towers which have low shear, low moment, and high axial
load. Pile capacity determination is thoroughly described in the AASHTO
LRFD Bridge Design Specifications (AASHTO, 2010, Section 10.7) for both
ASD and RBD approaches.
Anchors offer resistance to upward loads transferred from either steel
structure guy cables or the structure itself (tower leg or overturning
moment within a shallow foundation). The anchor may be a buried steel plate
or concrete slab or may be a grouted bar or cable within a drill hole.
Anchorages may be prestressed to limit deformation of the supporting structure.
Anchor capacity is usually designed based on the pull-out capacity of either
a wedge of soil (dead-man anchor types), the side resistance of anchor
rods, grouts, and surrounding soil/rock (grouted anchors), or both. The
IEEE/ASCE foundation design guide provides a more in-depth description
of anchor types and general design methods. Many manufactured anchor systems
provide proprietary design processes to be used with their products.

FIG. 4 Cylindrical side shear design model predicted nominal ultimate
uplift capacity, Rn, vs. interpreted test uplift capacity, RT, for drilled
shafts embedded in cohesive soils (D/B = 10).

FIG. 5 Relationship between resistance factor, Φ5, and coefficient of
variation, Vm.
3.4 Foundation Reliability-Based Design
The resistance factor, F5 (discussed in Section 2.2), can be determined
for a specific foundation design model by using a calibration
process. The process involves predicting the ultimate capacities of a given
number of full-scale foundation load tests using the design model to be
calibrated. FIG. 4 is an example of calibrating the cylindrical shear uplift
load design model using 48 full-scale drilled shaft uplift load tests,
where each drilled shaft is embedded in a cohesive soil.
The data presented in FIG. 4 show that the cylindrical shear uplift load
design model for drilled shafts embedded in cohesive soils has a 5% LEL
resistance factor, F5, of 0.67. This resistance factor is computed using
the following equation:
F5 m 5 m m 1 k V = - ( )
(eqn. 5)
where mm is the mean of the m-values for each test, wherein each m-value
equals test resistance divided by predicted nominal capacity Vm is the
coefficient of variation of the m-values As shown in FIG. 4, mm = 1.05
and Vm = 25.9% for the design model.
For a lognormal distribution of m, k5 is given by the following equation:
k 1 1 64 925V 5 m = - 0 0 0 00 . ( . . ),
(eqn. 6) where Vm is in percent.
Substituting with the preceding equations gives
F5 m m m m 1 = - × + × - -
( . . ) 1 64 10 9 25 10 2 5 2 V V (eqn. 7)
FIG. 5 provides plots of F5 vs. Vm for values of mm from 0.75 to 1.75.
The use of statistical data coupled with reliability theory meets the
objective of providing a consistent level of safety in design. This approach,
however, relies on a sufficient quantity and quality of test data
that, in many cases, is simply not available. When information is insufficient,
many agencies and organizations tasked with development of
resistance factors calibrate the results by curve-fitting of
ASD safety factors. Calibration by fitting to ASD also offers an opportunity
to adjust resistance factors developed from reliability theory to insure
design results similar to ASD where justified. Monte Carlo simulation has
also been used successfully for performing reliability analyses and developing
resistance factor.
No matter the method, estimation of foundation resistance factors must
involve the use of engineering judgment. Limited or low-quality data should
be taken into account in determining RBD methods. Poor or insufficient
data can result in overly conservative resistance factors that produce
designs in excess of ASD methods, thus discouraging designers in their
use. The fact that transmission foundations have historically performed
very well with relatively few failures indicates both success in the application
of electric system foundation design and the opportunity to provide more
economical and reliable designs in the future. |