.
1. Selecting a Monitoring Point
2. What to Monitor
3. Selecting a Monitor: Voltage • Voltage Waveform Disturbances
• Current Recordings • Current Waveshape Disturbances • Harmonics • Flicker
• High Frequency Noise • Other Quantities
4. Summary
Many power quality problems are caused by inadequate wiring or improper grounding.
These problems can be detected by simple examination of the wiring and grounding
systems. Another large population of power quality problems can be solved by
spotchecks of voltage, current, or harmonics using hand held meters. Some problems,
however, are intermittent and require longer-term monitoring for solution.
Long-term power quality monitoring is largely a problem of data management.
If an rms value of voltage and current is recorded each electrical cycle, for
a three-phase system, about 6 GB of data will be produced each day. Some equipment
is disrupted by changes in the voltage waveshape that may not affect the rms
value of the waveform. Recording the voltage and current waveforms will result
in about 132 GB of data per day. While modern data storage technologies may
make it feasible to record every electrical cycle, the task of detecting power
quality problems within this mass of data is daunting indeed.
Most commercially available power quality monitoring equipment attempts to
reduce the recorded data to manageable levels. Each manufacturer has a generally
proprietary data reduction algorithm. It’s critical that the user understand
the algorithm used in order to properly interpret the results.
1. Selecting a Monitoring Point
Power quality monitoring is usually done to either solve an existing power
quality problem, or to deter mine the electrical environment prior to installing
new sensitive equipment. For new equipment, it’s easy to argue that the monitoring
equipment should be installed at the point nearest the point of connection
of the new equipment. For power quality problems affecting existing equipment,
there is frequently pressure to determine if the problem is being caused by
some external source, i.e., the utility.
This leads to the installation of monitoring equipment at the service point
to try to detect the source of the problem. This is usually not the optimum
location for monitoring equipment. Most studies suggest that 80% of power quality
problems originate within the facility. A monitor installed on the equipment
being affected will detect problems originating within the facility, as well
as problems originating on the utility. Each type of event has distinguishing
characteristics to assist the engineer in correctly identifying the source
of the disturbance.
2. What to Monitor
At minimum, the input voltage to the affected equipment should be monitored.
If the equipment is single phase, the monitored voltage should include at least
the line-to-neutral voltage and the neutral to-ground voltages. If possible,
the line-to-ground voltage should also be monitored. For three-phase equipment,
the voltages may either be monitored line to neutral, or line to line. Line-to-neutral
voltages are easier to understand, but most three-phase equipment operates
on line-to-line voltages. Usually, it’s preferable to monitor the voltage line
to line for three-phase equipment.
If the monitoring equipment has voltage thresholds which can be adjusted,
the thresholds should be set to match the sensitive equipment voltage requirements.
If the requirements are not known, a good starting point is usually the nominal
equipment voltage plus or minus 10%.
In most sensitive equipment, the connection to the source is a rectifier,
and the critical voltages are DC. In some cases, it may be necessary to monitor
the critical DC voltages. Some commercial power quality monitors are capable
of monitoring AC and DC simultaneously, while others are AC only.
It’s frequently useful to monitor current as well as voltage. For example,
if the problem is being caused by voltage sags, the reaction of the current
during the sag can help determine the source of the sag. If the current doubles
when the voltage sags 10%, then the cause of the sag is on the load side of
the current monitor point. If the current increases or decreases 10%-20% during
a 10% voltage sag, then the cause of the sag is on the source side of the current
monitoring point.
Sensitive equipment can also be affected by other environmental factors such
as temperature, humidity, static, harmonics, magnetic fields, radio frequency
interference (RFI), and operator error or sabotage. Some commercial monitors
can record some of these factors, but it may be necessary to install more than
one monitor to cover every possible source of disturbance.
It can also be useful to record power quantity data while searching for power
quality problems. For example, the author found a shortcut to the source of
a disturbance affecting a wide area by using the power quantity data. The recordings
revealed an increase in demand of 2500 kW immediately after the disturbance.
Asking a few questions quickly led to a nearby plant with a 2500 kW switched
load that was found to be malfunctioning.
3. Selecting a Monitor
Commercially available monitors fall into two basic categories: line disturbance
analyzers and volt age recorders. The line between the categories is becoming
blurred as new models are developed.
Voltage recorders are primarily designed to record voltage and current strip
chart data, but some models are able to capture waveforms under certain circumstances.
Line disturbance analyzers are designed to capture voltage events that may
affect sensitive equipment. Generally, line disturbance analyzers are not good
voltage recorders, but newer models are better than previous designs at recording
voltage strip charts.
In order to select the best monitor for the job, it’s necessary to have an
idea of the type of disturbance to be recorded, and an idea of the operating
characteristics of the available disturbance analyzers. For example, a common
power quality problem is nuisance tripping of variable speed drives. Variable
speed drives may trip due to the waveform disturbance created by power factor
correction capacitor switching, or due to high or low steady state voltage,
or, in some cases, due to excessive voltage imbalance. If the drive trips due
to high voltage or waveform disturbances, the drive diagnostics will usually
indicate an overvoltage code as the cause of the trip. If the voltage is not
balanced, the drive will draw significantly unbalanced currents. The current
imbalance may reach a level that causes the drive to trip for input overcurrent.
Selecting a monitor for variable speed drive tripping can be a challenge. Most
line disturbance analyzers can easily capture the waveshape disturbance of
capacitor switching, but they are not good voltage recorders, and may not do
a good job of reporting high steady state voltage. Many line disturbance analyzers
cannot capture voltage unbalance at all, nor will they respond to current events
unless there is a corresponding voltage event. Most voltage and current recorders
can easily capture the high steady state voltage that leads to a drive trip,
but they may not capture the capacitor switching waveshape disturbance. Many
voltage recorders can capture voltage imbalance, current imbalance, and some
of them will trigger a capture of voltage and current during a current event,
such as the drive tripping off.
To select the best monitor for the job, it’s necessary to understand the characteristics
of the available monitors. The following sections will discuss the various
types of data that may be needed for a power quality investigation, and the
characteristics of some commercially available monitors.
===

FGR. 1 RMS voltage stripchart, taken cycle by cycle.
Maximum 1 cycle voltage -- 121 120.5 120 119.5 119 118.5
Minimum 1 cycle voltage Average of every cycle in recording interval FGR.
2 Min/Max/Average stripchart, showing the minimum single cycle voltage, the
maximum single cycle voltage, and the average of every cycle in a recording
interval. Compare to the FGR. 1 stripchart data.
===

FGR. 3 Cycle-by-cycle rms stripchart showing two voltage sags. The sag on
the left is due to an adjacent feeder fault on the supply substation, and the
sag on the right is due to a large motor start. Note the difference in the
voltage profile during recovery.

FGR. 4 Min/Max/Average stripchart of the same voltage sags as FGR. 3. Note
that both sags look almost identical. Without the recovery detail found in
FGR. 3, it’s difficult to determine a cause for the voltage sags.
Adjacent feeder fault voltage sag Large motor start voltage sag
====
Voltage
The most commonly recorded parameter in power quality investigations is the
rms voltage delivered to the equipment. Manufacturers of recording equipment
use a variety of techniques to reduce the volume of the data recorded. The
most common method of data reduction is to record Min/Max/Average data over
some interval. FGR. 1 shows a strip chart of rms voltages recorded on a cycle-by-cycle
basis.
FGR. 2 shows a Min/Max/Average chart for the same time period. A common recording
period is 1 week. Typical recorders will use a recording interval of 2-5 min.
Each recording interval will produce three numbers: the rms voltage of the
highest 1 cycle, the lowest 1 cycle, and the average of every cycle during
the interval. This is a simple, easily understood recording method, and it’s
easily implemented by the manufacturer. There are several drawbacks to this
method. If there are several events during a recording interval, only the event
with the largest deviation is recorded. Unless the recorder records the event
in some other manner, there is no time-stamp associated with the events, and
no duration available. The most critical deficiency is the lack of a voltage
profile during the event. The voltage pro file provides significant clues to
the source of the event. For example, if the event is a voltage sag, the minimum
voltage may be the same for an event caused by a distant fault on the utility
system, and for a nearby large motor start. For the distant fault, however,
the voltage will sag nearly instantaneously, stay at a fairly constant level
for 3-10 cycles, and almost instantly recover to full voltage, or possibly
a slightly higher voltage if the faulted section of the utility system is separated.
For a nearby motor start, the voltage will drop nearly instantaneously, and
almost immediately begin a gradual recovery over 30-180 cycles to a voltage
somewhat lower than before. FGR. 3 shows a cycle-by-cycle recording of a simulated
adjacent feeder fault, followed by a simulation of a voltage sag caused by
a large motor start.
FGR. 4 shows a Min/Max/Average recording of the same two events. The events
look quite similar when captured by the Min/Max/Average recorder, while the
cycle-by-cycle recorder reveals the difference in the voltage recovery profile.
Some line disturbance analyzers allow the user to set thresholds for voltage
events. If the voltage exceeds these thresholds, a short duration stripchart
is captured showing the voltage profile during the event. This short duration
stripchart is in addition to the long duration recordings, meaning that the
engineer must look at several different charts to find the needed information.
Some voltage recorders have user-programmable thresholds, and record deviations
at a higher resolution than voltages that fall within the thresholds. These
deviations are incorporated into the stripchart, so the user need only open
the stripchart to determine, at a glance, if there are any significant events.
If there are events to be examined, the engineer can immediately "zoom
in" on the portion of the stripchart with the event.
Some voltage recorders don’t have user-settable thresholds, but rather choose
to capture events based either on fixed default thresholds or on some type
of significant change. For some users, fixed thresholds are an advantage, while
others are uncomfortable with the lack of control over the meter function.
In units with fixed thresholds, if the environment is normally somewhat disturbed,
such as on a welder circuit at a motor control center, the meter memory may
fill up with insignificant events and the monitor may not be able to record
a significant event when it occurs. For this reason, monitors with fixed thresholds
should not be used in electrically noisy environments.
Voltage Waveform Disturbances
Some equipment can be disturbed by changes in the voltage waveform. These
waveform changes may not significantly affect the rms voltage, yet may still
cause equipment to malfunction. An rms-only recorder may not detect the cause
of the malfunction. Most line disturbance analyzers have some mechanism to
detect and record changes in voltage waveforms. Some machines compare portions
of successive waveforms, and capture the waveform if there is a significant
deviation in any portion of the waveform.
Others capture waveforms if there is a significant change in the rms value
of successive waveforms.
Another method is to capture waveforms if there is a significant change in
the voltage total harmonic distortion (THD) between successive cycles.
The most common voltage waveform change that may cause equipment malfunction
is the disturbance created by power factor correction capacitor switching.
When capacitors are energized, a disturbance is created that lasts about 1
cycle, but does not result in a significant change in the rms voltage.
FGR. 5 shows a typical power factor correction capacitor switching event.

FGR. 5 Typical voltage waveform disturbance caused by power factor correction
capacitor energization.

FGR. 6 RMS stripcharts of voltage and current during a large current increase
due to a motor start down stream of the monitor point. RMS voltage; RMS current
Current Recordings
Most modern recorders are capable of simultaneous voltage and current recordings.
Current recordings can be useful in identifying the cause of power quality
disturbances. For example, if a 20% voltage sag (to 80% of full voltage) is
accompanied by a small change in current (plus or minus about 30%), the cause
of the voltage sag is usually upstream (toward the utility source) of the monitoring
point. If the sag is accompanied by a large increase in current (about 100%),
the cause of the sag is downstream (toward the load) of the monitoring point.
FGR. 6 shows the rms voltage and current captured during a motor start downstream
of the monitor. Notice the large current increase during starting and the corresponding
small decrease in voltage.
Some monitors allow the user to select current thresholds that will cause
the monitor to capture both voltage and current when the current exceeds the
threshold. This can be useful for detecting over- and under-currents that may
not result in a voltage disturbance. For example, if a small, unattended machine
is tripping off unexpectedly, it would be useful to have a snapshot of the
voltage and current just prior to the trip. A threshold can be set to trigger
a snapshot when the current goes to zero. This snapshot can be used to determine
if the input voltage or current was the cause of the machine trip.
Current Waveshape Disturbances
Very few monitors are capable of capturing changes in current waveshape.
It’s usually not necessary to capture changes in current waveshape, but in
some special cases this can be useful data. For example, inrush current waveforms
can provide more useful information than inrush current rms data.
FGR. 7 shows a significant change in the current waveform when the current
changes from zero to nearly 100 A peak. The shape of the waveform, and the
phase shift with respect to the voltage waveform, confirm that this current
increase was due to an induction motor start. FGR. 7 shows the first few cycles
of the event shown in FGR. 6.

FGR. 7 Voltage and current waveforms for the first few cycles of the current
increase illustrated in FGR. 6.
Harmonics
Harmonic distortion is a growing area of concern. Many commercially available
monitors are capable of capturing harmonic snapshots. Some monitors have the
ability to capture harmonic stripchart data.
In this area, it’s critical that the monitor produce accurate data. Some commercially
available monitors have deficiencies in measuring harmonics. Monitors generally
capture a sample of the voltage and cur rent waveforms, and perform a Fast
Fourier Transform to produce a harmonic spectrum. According to the Nyquist
Sampling Theorem, the input waveform must be sampled at least twice the highest
frequency that is present in the waveform. Some manufacturers interpret this
to mean the highest frequency of interest, and adjust their sample rates accordingly.
If the input signal contains a frequency that is above the maximum frequency
that can be correctly sampled, the high frequency signal may be "aliased," that
is, it may be incorrectly identified as a lower frequency harmonic. This may
lead the engineer to search for a solution to a harmonic problem that does
not exist. The aliasing problem can be alleviated by sampling at higher sample
rates, and by filtering out frequencies above the highest frequency of interest.
The sample rate is usually found in the manufacturer's literature, but the
presence of an antialiasing filter is not usually mentioned in the literature.
Flicker
Some users define flicker as the voltage sag that occurs when a large motor
starts. Other users regard flicker as the frequent, small changes in voltage
that occur due to the operation of arc furnaces, welders, chippers, shredders,
and other varying loads. Nearly any monitor is capable of adequately capturing
voltage sags due to occasional motor starts. The second definition of flicker
is more difficult to monitor. In the absence of standards, several manufacturers
have developed proprietary "flicker" meters. In recent years, an
effort has been made to standardize the definition of "flicker," and
to standardize the performance of flicker meters. At the time of this writing,
several monitor manufacturers are attempting to incorporate the standardized
flicker function into their existing products.
High Frequency Noise
Sensitive electronic equipment can be susceptible to higher frequency signals
imposed on the voltage waveform. These signals may be induced on the conductors
by sources such as radio transmitters or arcing devices such as fluorescent
lamps, or they may be conductively coupled by sources such as power line carrier
energy management systems. A few manufacturers include detection circuitry
for high frequency signals imposed on the voltage waveform.
Other Quantities
It may be necessary to find a way to monitor other quantities that may affect
sensitive equipment.
Examples of other quantities are temperature, humidity, vibration, static
electricity, magnetic fields, fluid flow, and air flow. In some cases, it may
also become necessary to monitor for vandalism or sabotage. Most power quality
monitors cannot record these quantities, but other devices exist that can be
used in conjunction with power quality monitors to find a solution to the problem.
4. Summary
Most power quality problems can be solved with simple hand-tools and attention
to detail. Some problems, however, are not so easily identified, and it may
be necessary to monitor to correctly identify the problem. Successful monitoring
involves several steps. First, determine if it’s really necessary to monitor.
Second, decide on a location for the monitor. Generally, the monitor should
be installed close to the affected equipment. Third, decide what quantities
need to be monitored, such as voltage, current, harmonics, and power data.
Try to determine the types of events that can disturb the equipment, and select
a meter that is capable of detecting those types of events. Fourth, decide
on a monitoring period. Usually, a good first choice is at least 1 business
cycle, or at least 1 day, and more commonly, 1 week. It may be necessary to
monitor until the problem recurs. Some monitors can record indefinitely by
discarding older data to make space for new data. These monitors can be installed
and left until the problem recurs. When the problem recurs, the monitoring
should be stopped before the event data is discarded.
After the monitoring period ends, the most difficult task begins-interpreting
the data. Modern power quality monitors produce reams of data during a disturbance.
Data interpretation is largely a matter of experience, and Ohm's law. There
are many examples of disturbance data in books such as The BMI Hand book of
Power Signatures, Second Edition, and the Dranetz Field Handbook for Power
Quality Analysis. |