.From the service entrance of most industrial facilities power
is distributed by way of three-phase busway or wired into distribution
panels. Usually voltage at the service entrance is reduced via
transformer to three-phase 480VAC. Various fused disconnects or
circuit breakers are located to provide protection for branches
of the distribution system. Disconnects that can only be reached
by long poles with hooks at the end are often located at the point
of power drops to individual machines. Wiring is distributed inside
rigid conduit or EMT to fixed locations or in flexible Seal-Tite
or power cable to more temporary or movable spots. Cable tray is
often mounted from the ceiling with multiconductor control or power
cable laid in it and dropped to points of use. It is important
to consult the National Electric Code or local regulations when
planning a power distribution system.
Wire and cable are sized by the allowable amount of current that
they are rated to carry for certain conditions, such as temperature
or insulation. Wire is rated by gauge and may be sized in terms
of American wire gauge (AWG), standard wire gauge (SWG), or imperial
wire gauge. Wire is usually rated by Ampacity, another name for
the amount of current it can safely carry.
Relays and contactors are a form of switching device that applies
or removes power from a circuit based on a remote or external signal.
Timers and counters also switch power or signals based on a delay
or set number of pulses.
4.1 Disconnects, Circuit Breakers, and Fusing
An individual line of automation equipment or single machine will
typically have one main disconnect to allow power to be removed
from a single source. These disconnects usually have a set of fuses
or a circuit breaker rated appropriately for the equipment they
are supplying. There will often be several levels of branch circuit
protection after the main disconnect in the form of fuses or circuit
breakers. In most cases these also serve as a manual disconnect
for the branch, although some motor circuits will simply have a
fuse clip with no disconnecting means upstream. There are regulations
concerning disconnects being present within a certain distance
from a motor, so disconnects without fusing are sometimes located
nearby for quick power removal. Disconnects consist of a set of
contacts rated for the amount of current they must break with a
manual means of actuation. These may also include a means of remote
actuation or control.
Circuit Breakers
A circuit breaker is a circuit protection device that can be reset
after detection of an electrical fault. Like all circuit protection
devices, its purpose is to remove power from an electrical device
or group of devices, protecting the circuit from damage. Circuit
breakers are rated by the current at which they are designed to
trip, as well as the maximum current they can safely interrupt
during a short circuit.
Circuit breakers interrupt a current automatically; this requires
some kind of stored mechanical energy, such as a spring or an internal
power source, to actuate a trip mechanism. Small breakers such
as those used for branch circuit or component protection in a machine
are usually self-contained inside a molded plastic case. Larger
circuit breakers usually have a pilot device that senses a spike
in current and operates a separate trip mechanism. Current is detected
in several ways. Magnetic breakers route the current through an
electromagnetic circuit. As the current increases, the pulling
force on a latch also increases, eventually letting the contacts
open by spring action.
Thermal magnetic circuit breakers use a bimetallic strip to detect
longer-term over current conditions while using a magnetic circuit
to respond instantly to large surges, such as a short circuit.
Circuit breakers usually have a reset lever to manually trip and
reset the circuit. This is an advantage over using fuses, which
must be replaced after one use. In industrial applications most
circuit breakers are used for low-voltage application (under 1000
V). Medium-voltage (1000 to 72 k) and high-voltage (more than 72.5
kV) breakers are used in switchgear applications but are rarely
seen in industrial plants, though medium voltage switchgear is
used in some process facilities.
Low-voltage breakers may be of the DC or AC variety and generally
fall into the categories of miniature circuit breakers (usually
DIN rail mounted, up to 100 A) and molded case circuit breakers
(self contained, up to 2500 A). An example of a molded case breaker
is shown in FIG. 23.

FIG. 23 Molded case circuit breaker.
Circuit breakers must carry the designed current load without
overheating. They must also be able to withstand the arc that is
generated when the electrical contacts are opened. Contacts are
usually made of copper or a variety of alloys. Contact erosion
occurs every time the contacts are opened under load; usually miniature
circuit breakers are discarded when the contacts are worn, but
some larger breakers have replaceable contacts.
There are two types of trip units in low-voltage circuit breakers:
thermal magnetic and electronic. The thermal magnetic trip units
contain a bimetallic thermal device that actuates the opening of
the breaker with a delay depending on the overcurrent value. These
are used for overload protection. The magnetic trip device has
either a fixed or adjustable threshold that actuates the instantaneous
trip of the breaker on a predetermined overcurrent value-usually
a multiple of the overload current rating.
Electronic trip units use a microprocessor to process the current
signal. Digital processing provides four different trip functions:
the long and short time-delay trip functions per ANSI code 51 (AC
time overcurrent), the instantaneous trip function per ANSI code
50 (instantaneous overcurrent), and the ground-fault trip function
per ANSI code 51 N (AC time ground fault overcurrent).
Circuit breakers are categorized by their characteristic curves
for different applications. Highly inductive loads, such as transformers,
can have very high inrush currents of 10 to 20 times the current
rating of the device. These are classified as a class "D" curve.
Normal inductive loads, including most motors, have a current inrush
rating of 5 to 10 times the rating of the device and are classified
as a class "C" curve. A class "B" curve is
used for most lighter-duty noninductive loads and has a rating
of two to five times the circuit breaker rating.
Circuit breakers are also rated for use as branch, supplementary,
or feeder devices. Feeder circuit breakers are generally of the
molded case variety and are designed for main power feeds. They
are typically tested at 20,000A interrupting rating. Branch circuit
protection is tested for at least 5000 A interrupting rating and
is used for branch circuits under the main breaker. Feeder and
branch circuit breakers must be listed devices by Underwriters
Laboratories (UL).
Supplementary protection devices are used for equipment protection
in a branch circuit. They are classified as "recognized components" by
UL rather than listed. They are tested with upstream branch circuit
protection and are generally rated for 5000 A or less.
Motor circuit protectors (MCPs) are special application breakers
with adjustable magnetic settings. They allow the operator to set
the breaker's magnetic protection level just above the inrush level
of the motor. Overload protection for the motor is supplied in
the starter's overload relay. This combination allows protection
of the motor without causing nuisance trips. MCPs are UL-recognized
components.
Motor protector circuit breakers (MPCBs) are UL-listed circuit
breakers with fixed magnetic protection and built-in motor overload
protection. These breakers' trip units are adjustable for Motor
FLA ratings and can be set for overload trip class. MPCBs can be
used directly with a contactor for a complete motor starting and
protection package.
Fuses
A fuse or fusible link is an overcurrent protection device that
is designed to melt (or "blow") when excessive current
flows through it. It is composed of a metal strip or wire element
rated at a specified current plus a small percentage. This is mounted
between two electrical terminals and generally surrounded with
a nonflammable insulating housing.
Fuses are placed in series with the current flow to a branch or
device. If the current flow through the element becomes too high,
enough heat is generated to melt the element itself or a solder
joint within the fuse.

FIG. 24 Cartridge fuses.
Dual element fuses contain a metal strip that melts instantly
for a short circuit as well as a low melting solder joint for longer-term
overloads. Time delay or "slow blow" fuses allow short
periods of overcurrent conditions and are used for motor circuits,
which can have a higher current inrush as the motor starts.
Fuses are made in many different shapes, sizes, and materials,
depending on the manufacturer and application. While the terminals
and fuse element must be made of a metal or alloy for conductivity,
the fuse body may be glass, fiberglass, ceramic, or insulating
compressed fibers. Fuse sizes and mounting methods generally fall
into several standardized formats. FIG. 24 shows several cartridge
type fuses; note that the larger fuse on the left has an indented
area or groove at the bottom end of the fuse. This is known as
a rejection fuse, the feature ensures that the fuse can only be
placed into its holder one way.
Most fuses used in industrial applications are cartridge fuses.
These are cylindrical with conducting caps on each end separated
by the fusible link covered by the housing. These may be small
glass or ceramic fuses for light loads or larger J or R class fuses.
Cartridge fuses are also known as ferrule fuses. The caps may have
bladed ends for insertion into clips or have a hole in the blade
for bolting to a terminal. The most common methods are spring clips
or terminal block-style fuse holders.
Fuses for use on printed circuit boards (PCBs) are generally soldered
into place. They may have wire leads or solder pads depending on
the desired mounting technique.
Fuses Compared with Circuit Breakers
Fuses are less costly than circuit breakers but must be replaced
every time an overcurrent event occurs. This is not as convenient
as simply resetting a breaker, though, and makes it more difficult
to ignore intermittent faults.
Fuses react more quickly than circuit breakers, especially the "current-limiting" variety.
This helps minimize the damage to downstream equipment.
4.2 Distribution and Terminal Blocks
Cable and wire is distributed to multiple circuits by terminating
the ends into a securing means such as a screw or clamp. Distribution
blocks are used for larger gauges of wire. They are usually connected
by means of screwing a threaded stud into a block of metal. One
side will have one termination point and the other will have multiples
to feed branch circuits. Distribution blocks are mounted into insulating
carriers with dividers between phases and are available in one
to four pole configurations. They can have one or more terminations
for each pole on the incoming side and up to 12 terminations each
on the outgoing or branch side. FIG. 25 shows a three-phase open-style
distribution block; there are six connections for each phase. Wire
gauges start at around 14 AWG and go all the way up into large
MCM-size cable. MCM is an abbreviation for thousand circular mil
(a mil is a thousandth of an inch).
Multiterminal copper or aluminum bus bars with a series of screw
terminals are often used for ground or neutral terminations in
panels.
These are typically for smaller wire sizes that have no voltage
present.
Terminal blocks are used to make wiring and cable connections
and manage wiring. They are sized for the ranges of the wire and
cables that are to be connected. Screw terminal and spring clamp
types are both widely used on smaller conductors, but for large
wire sizes screw terminals are usually used.

FIG. 25 Distribution block.
There are a wide variety of styles and manufacturers of terminal
blocks. The main purpose of terminal blocks other than wire management
is to insulate the exposed wiring ends when making connections.
The National Electrical Manufacturers Association (NEMA) has a
number of standards associated with terminal block specifications
as does the International Electrotechnical Commission (IEC). Terminal
blocks are often categorized as being NEMA or IEC style. NEMA terminal
blocks are typically a more open style, while IEC is considered
a "finger-safe" style with insulation surrounding the
screw or clamp terminals.
Terminal blocks are generally sized to mount on uniform-size metal
rails known as DIN rail. DIN is an abbreviation for Deutsches Institut
für Normung, a German standard. FIG. 26 shows a selection of various
types of labeled IEC terminal blocks mounted on a piece of DIN
rail. The larger black block is a cartridge fuse-holding terminal
block.
Usually connections are straight through the block from terminal
to terminal, but removable jumpers, switches, or fuses are sometimes
built into the block. Terminal blocks for fuses are also called
fuse blocks. These are made to swing open for fuse removal and
also double as a branch or component disconnect. LED indicators
are also embedded in some terminal blocks for energy presence or
blown fuse indication. Special-purpose terminal blocks with contacts
for thermocouples and extremely low or high voltages are also available.
Terminal blocks are commonly available in one-, two-, and three
level configurations as a space-saving feature. They are usually
mounted to some type of metal rail, the most common being DIN rail.
This allows blocks from different manufacturers to be mounted
on a common surface. They are made in a wide variety of colors,
which are often used for circuit identification.
A wide range of accessories are available for terminal blocks,
including center and side jumpers to form a common bus, DIN rail,
labels and labeling kits, and end caps and anchors.

FIG. 26 IEC Terminal blocks on DIN rail.
4.3 Transformers and Power Supplies
Transformers are used to isolate or transfer energy in the form
of AC current from one circuit to another. This is done by the
principle of mutual inductance. If a changing current is passed
through a coil of wire, it creates a magnetic field that can be
used to create a current in another coil of wire that is electrically
isolated from the first coil. This is most often accomplished by
wrapping both coils around a common core of iron rich metal.
One of the principles of this induced voltage is that the voltage
can be raised or lowered in proportion to the number of turns in
the coils.
A formula that can be used to express this relationship is Vp/Vs
= Np/Ns, where V is voltage, N is the number of turns in the coil,
p is the primary or the coil where the voltage is applied, and
s is the secondary where the converted voltage is applied to the
load.
A transformer that is used to increase the voltage from the primary
to the secondary is known as a "step-up" transformer,
and the opposite is a "step-down" transformer. Of course,
by Ohm's law, when the voltage is increased, the current will be
decreased accordingly and vice versa.

FIG. 27 Transformer wiring diagram.
FIG. 27 is a wiring diagram for a single-phase power transformer.
Transformers can typically be "tapped" or wired in different
ways, as shown in this diagram. This particular transformer can
provide 480 to 120, 480 to 240, 240 to 120, and 240 to 240 voltage
conversions.
Transformers are also used for isolation purposes, as shown in
the 240 to 240 wiring (which could also be 120 to 120). Since a
voltage cannot change instantaneously through an inductor, isolation
transformers are often used to protect the load from quick spikes
in a circuit. They are commonly used in control and drive systems.
Transformers come in a wide range of sizes, from small internally
mounted transformers inside devices such as DC power supplies to
large three-phase transformers that power an entire production
line or section of a plant. Many commercially available transformers
have multiple taps, allowing the same transformer to provide a
range of voltages depending on how these taps are connected.
Another method of obtaining different voltages from one transformer
is to use an autotransformer. This is a transformer that only has
one winding with taps on each end and one at an intermediate point.
Voltage is applied to two of the terminals. The secondary is then
taken from one of the primary terminals and the third terminal.
The location of the intermediate tap determines the windings ratio
and therefore the output voltage. If insulation is removed from
part of the windings, the intermediate tap can be made movable
using a sliding brush, making the output voltage variable similar
to a potentiometer.
The purpose of a transformer in an automation system is either
to convert an AC voltage to a different voltage for distribution
in the system or to isolate a circuit from another. Commonly three-phase
480VAC is applied to the disconnect of a control enclosure. From
the disconnect power is distributed through various branches with
circuit protection for different purposes. Where a lower voltage
(usually 240,208 or 120VAC) is required, a transformer is connected
to reduce the voltage level. Transformers may be used between individual
phases to develop a single-phase voltage or across all three phases.
Windings are often tapped in the center and grounded to develop
two phases 180° out of phase with each other. This is similar to
a common residential service entrance, where 240VAC is wired to
a distribution or breaker panel along with a neutral (the grounded
center tap). The 240 V can then be used for higher-power appliances
and two rows of breakers supply 120VAC to branch circuits.
Transformers typically have circuit protection such as fuses or
power supplies on both the primary and secondary side.
DC power supplies are used to provide lower-voltage DC power for
I/O devices such as sensors and solenoid valves. Power supplies
usually have regulated outputs to prevent current or voltage fluctuations.
They are usually protected on the AC and DC sides by fuses or circuit
breakers.
The most common voltage used for industrial machinery is 24VDC.
This is a low enough voltage to prevent most injuries but high
enough to minimize noise interference and allow distribution over
a reasonable distance. 12VDC is also sometimes used, while higher
DC levels of 48 or more volts may be used for DC motors such as
steppers. Servos and DC motors do not usually use separate power
supplies, but generate their own DC power in the drive.
4.4 Relays, Contactors, and Starters
A relay is a device that allows switching of a circuit by electrical
means. There are various types of relays, including electromechanical
and solid-state coils, reed or mercury wetted contact, but the
purpose is generally the same: to control a circuit with one voltage
with a signal from another or to use one signal to switch multiple
circuits, as in FIG. 28.
Electromechanical relays use an electromagnetic coil to physically
pull a set (or sets) of contacts either from an open to a closed
position or from closed to open. AC or DC may be used to switch
the coil; this is one of the specifications of a relay along with
the number of poles and amount of current that can be handled by
the contacts. Contacts are specified as NO or NC, referring to
their deenergized state. Relays may have multiple poles of both
NO and NC contacts. FIG. 29 shows a variety of different relay
types; the relay to the far left is a tube-base electromechanical
relay and socket, and the next two are often referred to as "ice-cube" relays.
The relay on the lower right is a heavier-duty DIN rail mount electromechanical
relay, while the one at the upper right is an adjustable timing
relay.

FIG. 28 Schematic of four pole relay.

FIG. 29 Relays.
Solid-state relays use transistor technology to switch current
flow.
Voltage is applied to a solid-state "coil" that may
switch current directly through a transistor or CMOS device or
energize an LED to optically isolate the circuits. Solid-state
relays have no moving parts, which gives them greater longevity
than electromechanical relays; however, they are rated at a lower
current-switching capability.
Some relays have a coil to latch the relay on and a separate coil
to reset it. These are used when a circuit state needs to be maintained
even if power is lost. These are known as latching or set-reset
(SR) relays.
Safety circuits often use relays that have force-guided contacts.
This means that the contacts are mechanically linked together
so that all of them switch together. This ensures that if a set
of contacts weld together because of arcing, then one set of contacts
can be used to reliably monitor the state of the relay. These safety
relays also use redundant sets of contacts for each circuit for
the same reason.
Relays come in a variety of form factors also. Large relays generally
are screw or bolt mounted directly to a panel or backplane, while
many standard industrial relays have round pins or blades that
can be plugged into a DIN rail-mounted socket. Sockets are available
in tube base for round pins and bladed base or pin sockets for
small relays. Small relays may also be soldered to a circuit board.
A type of relay that can handle the high power required to directly
control an electric motor is called a contactor. Continuous current
ratings for common contactors range from 10 A to several hundred
amps. Contactors are an element of motor starters; a motor starter
is simply a contactor with overload protection devices attached.
The overload sensing devices are a form of heat operated relay
where a coil heats a bimetal strip, or where a solder pot melts,
releasing a spring to operate an auxiliary set of contacts. These
auxiliary contacts are in series with the coil. If the overload
senses excess current in the load, the coil is deenergized.
Motor starters are generally categorized as NEMA or IEC style.
NEMA starters are generally larger and have replaceable overload
elements. They can generally be rebuilt if necessary; however,
they are physically larger and more expensive than an IEC motor
starter of the same rating. IEC starters are not usually rebuilt
and are simply discarded when the contacts wear out. FIG. 30 is
an IEC motor starter in a manual motor control enclosure.
4.5 Timers and Counters
A timer reacts to an applied signal or power feed and switches
a set of contacts based on a delay. It may also create a repetitive
series of pulses. Timers may be purely mechanical, such as with
a pneumatic timer; electromechanical with a motor and clutch; or
entirely electronic. They are available in both analog and digital
formats.
Timers generally fall into the following categories:
On Delay-Timer changes state after a specified period of • time
and remains in that state until the signal is removed.
Off Delay-Timer changes state immediately and reverts to • its
original state after a specified period of time.
One Shot-Timer creates a single pulse of specified length. •
Pulse or Repeat-Cycle-Timer creates a series of on and off • pulses
with configurable on and off times until signal is removed.
As with temperature controllers, timers and counters are often
sized using the DIN system, ensuring that they will fit a certain-size
panel cutouts. They are usually available in 1/16 DIN, 1/8 DIN,
or 1/4 DIN sizes. FIG. 31 shows a 1/16 DIN digital timer.

FIG. 30 IEC motor starter.

FIG. 31 1/16 DIN digital timer. (Courtesy of Omron.) FIG. 32
Eagle Signal electromechanical timer.
Electromechanical timers such as the Eagle Signal Cycle Flex timer
shown in FIG. 32 are often used in applications where electronic
timers may not be appropriate. Mechanically switched contacts may
still be less expensive than the semiconductor devices needed to
control powerful lights, motors, and heaters. An electromechanical
cam timer uses a small synchronous AC motor turning a cam against
a bank of switch contacts. The AC motor is turned at an accurate
rate by the applied frequency, which is regulated very accurately
by the power companies. Gears drive a shaft at the desired rate
and turn the cam. These timers are still in use in many industrial
facilities because they are easily rebuilt, rugged, and switch
high-current loads; however, they are often replaced with less
expensive and more reliable electronic timers.

FIG. 32. Eagle Signal Cycle Flex timer
The most common application of electromechanical timers now is
in washers, driers, and dishwashers. This type of timer often has
a friction clutch between the gear train and the cam, so that the
cam can be turned to reset the time. This is a less expensive method
of performing multiple timing segments with high-current load switching
than with an electronic version.
A counter also reacts to input signals, totalizing them and changing
the state of a signal when the specified count has been reached.
Counters are generally classified as up counters, where state changes
increment the value until the set point is reached, or down counters,
where the counter starts at the set point and counts down to 0.
Counters may also be combinational with both up and down signals.
Counters also have a reset input to set the counter back to its
starting point. They may be mechanical in nature, such as with
a totalizer, or be incremented electronically.
4.6 Push Buttons, Pilot Lights, and Discrete Controls
Before the advent of touch screens, signaling and machine control
had to be done with push buttons, switches, and indicator lights.
A large variety of components are still used as discrete interfaces
between an operator and a machine today.
Push Buttons and Switches
A push button is a manually operated spring-loaded method of opening
or closing a set of electrical contacts. Industrial push buttons
generally come in several standard sizes; 30 mm, 22 mm, and 16
mm diameters. There are larger and smaller sizes also available,
but the vast majority of push buttons, switches, and pilot lights
fall within these standard sizes.
Larger push buttons (22 and 30 mm) are often modular in nature,
having an actuator to which contact blocks can be mounted and removable
mounting rings and bezels. Contact blocks are available in NO and
NC configurations and may be mixed and matched as necessary. These
blocks can also be stacked on top of each other for up to four
sets of contacts. Push buttons may also have an internal light
that may be illuminated from a control output or through one of
the sets of contacts; these are usually LED or incandescent bayonet
base bulbs.
Push buttons come in various colors, generally black, red, yellow,
green, blue, or white, although other colors are also sometimes
seen.
The actuator may be mushroom head, extended, or flush with the
bezel. They also may be of the momentary (spring return) or maintained
(toggling) variety. FIG. 33 is a 30 mm flush push button.
Selector switches have many of the same characteristics as push
buttons; they use the same types of contact blocks and come in
the same 16, 22, and 30 mm diameters. The color is usually black,
although inserts may be of various colors. Lights are not commonly
used in selector switches.
As with push buttons, switches may be of the maintained or spring
return variety. Most switches have two or three positions, although
four positions or even more are sometimes seen. Unlike push buttons,
however, all of the contacts do not switch at the same time. For
a three-position switch the contacts on one side will switch in
the left position and the opposite side will switch in the right
position. Both sides usually remain unswitched in the center.
Contact blocks are actuated with a cam rotating with the switch
body.
Part of the push button or selector switch assembly is usually
an antirotation ring. This is a ring with a tab that fits into
a slot in the device and also a tab that fits into a slot cut into
the punched hole in the cabinet or enclosure.

FIG. 33 30 mm push button.
Pilot Lights and Stack Lights
Pilot lights are available in the same standard sizes as push
buttons and switches, although much larger lights are sometimes
used for greater visibility and small 8 mm and 10 mm lights are
common for higher-density display. Lamps for pilot lights are generally
of the incandescent or LED type. Most lamps are white and a plastic
cover is used to change the color of the light. They are available
for "full voltage" applications of 120 to 240VAC, which
use a small transformer, as well as 12 and 24VDC. For low-voltage
or computer card outputs, 5 and 6VDC lamps are often used. Some
pilot lights also have a spring-loaded "push to test" feature
that will illuminate the lamp, although there are no external contacts
for these as there would be on a lighted push button. If pilot
lights are connected to controlled outputs, a separate "push
to test" push button is sometimes
used to illuminate all of the lamps on a panel at once.
Stack lights, also called light stacks or tower lights, are columnar
sets of lights that usually indicate the state of a whole machine
or control system. They are also modular, usually beginning with
a base unit that may or may not include a horn or buzzer. The base
may be connected using a quick disconnect cable or terminals with
a strain relief entry. Light units are then stacked onto the base
in the required order, generally up to five units in height. A
common combination of lights would be red, yellow, and green (from
top to bottom), red generally signifying a fault or alarm, yellow
signifying either caution or manual/maintenance mode, and green
signifying auto mode or machine running. There is no universal
stand for these colors, and each company or plant may have their
own specifications. Blinking the lights to signify auto/not started
or cycle stop versus immediate stop conditions is an example of
how a stack light might be used to deliver additional information.
Blue or white lights are sometimes added for signals like low bin
or hopper or other special functions as defined by the designer.
FIG. 34 shows several arrangements of four-color stack lights;
the two rightmost stacks have a buzzer or audible alert in the
top position.

FIG. 34 Stack lights. (Courtesy of Banner.)
As with pilot lights, they may be energized by 24VDC, 120VAC,
or various other voltages as required. Other modules for playing
a recorded voice or music are also available. A feature of some
stack lights that may be beneficial is a flexible base to reduce
the chance of the stack breaking off a low-mounted cabinet or machine.
Stack lights may also be pole mounted and side mounted, depending
on the application.
Other Panel-Mounted Devices
Some items grouped under the heading "discrete controls" may
not be discrete at all. An example is a panel-mounted potentiometer
for analog speed control of a motor drive. These are often available
in the same form factors as selector switches in 22 mm or 30 mm
sizes.
Temperature controllers, timers, and counters are also devices
you might find mounted on the front of a controls enclosure.
Horns and buzzers are other discrete devices that may be panel
mounted. Buzzers are generally piezoelectric and susceptible to
moisture since they cannot be easily sealed.
Along with all of the devices that might be mounted on a controls
enclosure come labels for these devices. Most commonly engraved
plastic tags or painted metal tags that have the appropriate-size
hole are used with push buttons, switches, and pilot lights. Engraved
plastic or metal tags are of two colors, an inside and outside
color. An example is Gravoply plastic, which may be black or red
on the outside with a white inside color. When characters are cut
into the plastic, the inside color shows through. Tags may be premade
with common terms like stop, start, and so on, or be sold as blanks
for the user to engrave.
Tags are not only used for devices on the outside an enclosure;
they are also common inside the cabinet or mounted next to a sensor
on a machine. These may be engraved or printed and contain schematic,
I/O, or descriptive text for components. Safety warnings also fall
into the premade or purchased label category.
4.7 Cabling and Wiring
An important part of the distribution of power and signals throughout
a system is cable and wire. Individual wires and multiconductor
cables are used to connect the various control devices and distribution
components within a machine or system. Wire sizes or gauges are
specified as described in the appendixes of this book. Wire may
be made of any conductive metal but is usually copper or aluminum.
Usually it is covered with a thermoplastic insulation available
in a wide range of colors. Wire is manufactured in solid or stranded
forms, depending on the application.
Multiconductor cables consist of a collection of insulated wires
inside a protective jacket. The wires may be twisted together in
pairs for noise immunity or simply run in parallel. Multiconductor
cables often carry a noninsulated shield or drain wire to help
carry away unwanted stray signals. This wire should be grounded
at one end only to prevent a ground loop. An additional foil covering
is often wrapped around the bundle inside the jacket but in contact
with the shield wire.
Examples of several multiconductor cables are shown in FIG. 35.
For high-flexing and repetitive movement applications, multiconductor
cable is often made with fine stranding to improve its bend radius
and increase usable lifetime. Specifications for expected number
of cycles and minimum bend radius are often listed in wiring catalogs.
Connecting individual wires or multiconductor cables together
may be done with terminal blocks, but in some cases they must be
spliced. This may be done using crimp on malleable metal pieces
called butt splices or wires may be soldered. After soldering,
the wire junction must be insulated using electrical tape or shrinkable
tubing, also known as heat shrink.

FIG. 35 Multiconductor cables.
Strain Relief
To prevent pulling wire and cabling out of terminations a strain
relief-type fitting is placed at enclosure entry points and built
into cable plugs. These may be of a screw clamp type or a rubber "donut" shape
that clamps down on the cable when a fitting is tightened.
Another type of strain relief has a series of ridges at the point
where the cable meets the enclosure or junction box. The main purpose
of a strain relief is to reduce wear or stress at the point of
entry when a cable is pulled. Strain reliefs often also provide
ingress protection from liquids. Strain reliefs often come in standard
hole sizes like electrical fittings; 3/8 in, 1/2 in, and 3/4 in.
One inch and larger are all standard sizes. They may be made of
a galvanized metal or plastic.
FIG. 36 illustrates a 1/2-in cord grip strain relief installed
in the side of an enclosure.

FIG. 36 Cord grip strain relief. (Courtesy of Thomas & Betts.)
Ferrules
A ferrule is a circular clamp or sleeve used to hold together
and attach fibers or wires by crimping the ferrule to permanently
tighten it onto the wire end. Wiring ferrules often have a color-coded
piece of plastic molded around one end both to allow easy wire
entry and for identification of wire gauge. Ferrules prevent smaller
stranded wires from splaying and provide a solid electrical connection
for terminal block clamps or screws. Special crimping tools with
selectable dies are used to crimp the ferrule firmly onto the exposed
wire end. FIG. 37 shows several different sizes of insulated ferrules.

FIG. 37 Ferrules.
Soldering
A common method of attaching wires to each other or to pins in
plugs is soldering. It is used in electronics, where it is used
to connect electrical wiring and to connect electronic components
to PCBs.
Soldering is also used in plumbing to connect metal piping together
with a water and gas tight bond.
Solder is a metal filler material that melts at a low temperature.
For electrical connections it is usually composed of tin and lead
in various proportions, the most common being 63 percent tin and
37 percent lead. This proportion also has the benefit of being
eutectic, meaning it passes directly from a liquid phase to a solid
phase. This is important because metals that pass through an intermediate "plastic" phase
are subject to cracking if disturbed while cooling.
Other alloys used for electrical connections are lead-silver for
higher strength, tin-zinc or zinc aluminum for joining aluminum,
and tin-silver and tin bismuth for other electronics. These alloys
all melt at a lower temperature than the materials they are joining.
This is the major difference between soldering and welding, which
melts part of the workpiece. All of these alloys are known as soft
solder, although silver solders are sometimes excepted from this
classification.
The process of soldering involves melting the solder and flowing
it into the joined wires or components. This process can be assisted
by using a rosin water-based or "no-clean" type of "flux" to
coat the joined pieces; solder flows to wherever the flux is applied.
Many solders have a flux core that helps in this process. In addition
to assisting the solder to flow, flux also helps clean the materials
and prevent oxidation. When soldering stranded wires, solder is
usually applied to the wire ends individually first; this is known
as tinning the wires. If flux is applied to the strands beforehand
or as part of the solder core, solder is drawn up into the strands
by capillary action, called wicking.
Soldering by hand is done with a soldering iron, which is an electrically
heated tool with an insulated handle and various different sizes
of tip. Many of these have a temperature adjustment for different-size
work. FIG. 38 shows a soldering iron and roll of rosin-core solder.
Often when soldering solid-state components, a clip-on "heat
sink" is used between the wire lead and the component to prevent
damage; proper temperature and tip size are important here also.

FIG. 38 Solder and soldering iron.
Soldering of components to PCBs on a production line is done by
a process known as wave soldering. Components are adhesively attached
to the board with leads extending through holes in the board and
touching contact pads. The boards are then passed over pools of
molten solder, which are vibrated, creating waves. This allows
solder to contact the pads and leads without immersing the entire
underside of the circuit board.
Another method of production soldering is to apply a solder powder
and flux mixture in little clumps to the solder joint. This can
then be melted with a heat lamp, hot air pencil, or most commonly
in an oven. This method is called reflow soldering.
Often a combination of wave, reflow, and hand soldering will be
used on the same PCB.
|