..
1. Introduction
As we had seen in the previous section, grounding of supply system neutral
fulfills two important functions.
- It provides a reference for the entire power system to the groundmass
and establishes a path for flow of currents to ground whenever there
is a failure of insulation so that the fault can be detected by circuit
protective devices and isolated.
- It ensures that in the event of an accidental connection of live parts
to a conducting metallic enclosure, any person coming into contact
with the enclosure does not experience dangerously high voltages. This
is done by bonding the enclosure to the ground so that the enclosure's
potential is firmly 'clamped' to that of the ground. Also, bonding of
all exposed metal parts in a building and connecting them to ground creates
an equipotential environment where all such parts will be essentially
at the same potential as the ground.
In this section, we will learn about the various types of grounding an
electrical system and their relative advantages. As you may recall from
the previous section, grounding of both source and the consumer equipment
is necessary. What we will see in this section is about the grounding of
the power source.
Note: We will be discussing in this as well as in the subsequent sections
electrical systems of three-phase configuration since for all practical
purposes, this is the only configuration that utilities all over the world
adopt. Systems of single-phase configuration will, however, be used in
illustrations for simplicity. FIG. 1 shows the various types of grounding
methods that are possible.
The diagrammatic representation of these different grounding techniques
and the equivalent impedances are shown in FIG. 2. We will go through in
detail about each method in the subsequent paragraphs.

FIG. 1 Grounding methods

FIG. 2 Grounding techniques and equivalent impedances
Grounding of power supply system neutral 15
2. Ungrounded systems
As discussed in Section 1, providing a reference ground in an electrical
system is essential for safe operation. But there are certain cases in
which a system can be operated without such a reference.
By definition, an electrical system, which is not intentionally connected
to the ground at any point, is an ungrounded system. However, it should
be noted that a connection to ground of sort does exist due to the presence
of capacitances between the live conductors and ground, which provides
a reference. But these capacitive reactances are so high that they cannot
provide a reliable reference. FIG. 3 illustrates this point. In some cases,
the neutral of potential transformer primary windings connected to the
system is grounded, thus giving a ground reference to the system.

FIG. 3 A virtual ground in an ungrounded system
It may be noted that normally the capacitance values being equal to the
lines L1 and L2 are roughly at a potential equal to half the voltage of
the source from the ground (it is possible to demonstrate this by measurement
of a high-impedance device such as an electrostatic type of voltmeter).
The main advantage cited for ungrounded systems is that when there is a
fault in the system involving ground, the resulting currents are so low
that they don’t pose an immediate problem to the system. Therefore, the
system can continue without interruption, which could be important when
an outage will be expensive in terms of lost production or can give rise
to life-threatening emergencies.
The second advantage is that one need not invest on elaborate protective
equipment as well as grounding systems, thus reducing the overall cost
of the system. (In practice, this is however offset somewhat by the higher
insulation ratings which this kind of system calls for due to practical
considerations.)
The disadvantages of such systems are as follows:
• In all but very small electrical systems, the capacitances, which exist
between the system conductors and the ground, can result in the flow of
capacitive current at the faulted point which can cause repeated arcing
and buildup of excessive voltage with reference to ground. This is far
more destructive and can cause multiple insulation failures in the system
at the same instant.
• The second disadvantage in practical systems is that of detecting the
exact location of the fault, which could take far more time than with grounded
systems.
This is because the detection of fault is usually done by means of a broken
delta connection in the voltage transformer circuit ( FIGs. 4a and b).
This arrangement does not tell where a fault has occurred and to do so,
a far more complex system of ground fault protection is required which
negates the cost advantage we originally talked about.
• Also, a second ground fault occurring in a different phase when one
unresolved fault is present, will result in a short circuit in the system.
Due to these overwhelming disadvantages, very rarely, if ever, distribution
systems are operated as ungrounded.

FIG. 4a Detection of ground fault using a broken delta connection - under
normal condition
3. Solidly grounded systems
As is evident from the name, a solidly grounded system is one where the
neutral of the system is directly connected to ground without introducing
any intentional resistance in the ground circuit. With appropriate choice
of the type and number of grounding electrodes, it’s possible to obtain
a very low-impedance ground connection, sometimes as low as 1 ohm. A solidly
grounded system clamps the neutral tightly to ground and ensures that when
there is a ground fault in one phase, the voltage of the healthy phases
with reference to ground does not increase to values appreciably higher
than the value under the normal operating conditions.
When there is an Earth fault in line A it assumes Earth Potential.
Therefore Voltage across PT primary windings become
ABBA, CCA V 0, V =V ,V =V =
Thus Secondary Vectors are
abba, cca V 0, V =V ,V =V =

FIG. 4b Detection of ground fault using a broken delta connection - under
Ground Fault condition
The advantages of this system are:
• A fault is readily detected and therefore isolated quickly by circuit
protective devices. Quite often, the protection against short circuit faults
(such as circuit breakers or fuses) is adequate to sense and isolate ground
faults as well.
• It’s easy to identify and selectively trip the faulted circuit so that
power to the other circuits or consumers can continue unaffected (contrast
this with the ungrounded system where a system may have to be extensively
disturbed to enable detection of the faulty circuit).
• No possibility of transient over-voltages.
The main disadvantage is that when applied in distribution circuits of
higher voltage (5 kV and above), the very low ground impedance results
in extremely high fault currents almost equal to or in some cases higher
than the system's three-phase short circuit currents.
This can increase the rupturing duty ratings of the equipment to be selected
in these systems.
Such high currents may not have serious consequences if the failure happens
in the distribution conductors (overhead or cable). But when a fault happens
inside a device such as a motor or generator such currents will result
in extensive damage to active magnetic parts through which they flow to
reach the ground.
For these reasons, use of solid grounding of neutral is restricted to
systems of lower voltage (380 V/480 V) used normally in consumer premises.
In all the other cases, some form of grounding impedance is always used
for reducing damage to critical equipment components.
4. Impedance grounding using neutral reactor
In this method of grounding, an inductor (also called a grounding reactor)
is used to connect the system neutral to ground. This limits the ground
fault current since it’s a function of the phase to neutral voltage and
the neutral impedance. It’s usual to choose the value of the grounding
reactor in such a way that the ground fault current is restricted to a
value between 25 and 60% of the three-phase fault current to prevent the
possibility of transient over-voltages occurring. Even these values of
fault current are high if damage prevention to active parts (as seen above)
is the objective.
5. Resonant grounding using neutral reactor
To avoid the problem of very high ground fault currents, the method of
resonant grounding can be adopted. Resonant grounding is a variant of reactor
grounding with the reactance value of the grounding reactor chosen such
that the ground fault current through the reactor is equal to the current
flowing through the system capacitances under such fault condition. This
enables the fault current to be almost canceled out resulting in a very
low magnitude of current, which is in phase with the voltage. This serves
the objectives of low ground fault current as well as avoiding arcing (capacitive)
faults, which are the cause of transient over-voltages. The action is explained
in FIG. 5.

FIG. 5 Resonant grounding
This type of grounding is common in systems of 15 kV (primary distribution)
range with mainly overhead lines but is not used in industrial systems
where the reactor tuning can get disturbed due to system configuration
changes caused by switching on or off cable feeders (with high capacitive
currents) frequently.
6. Impedance grounding through neutral resistance
This is by far the most common type of grounding method adopted in medium
voltage circuits. The system is grounded by a resistor connected between
the neutral point and ground. The advantages of this type of grounding
are as follows:
• Reducing damage to active magnetic components by reducing the fault
current.
• Minimizing the fault energy so that the flash or arc blast effects are
minimal thus ensuring safety of personnel near the fault point.
• Avoiding transient over-voltages and the resulting secondary failures.
• Reducing momentary voltage dips, which can be caused if, the fault currents
were higher as in the case of a solidly grounded system.
• Obtaining sufficient fault current flow to permit easy detection and
isolation of faulted circuits.
Resistance grounding can again be sub-divided into two categories, viz.
high-resistance grounding and low-resistance grounding.
High-resistance grounding limits the current to about 10 A. But to ensure
that transient over-voltages don’t occur, this value should be more than
the current through system capacitance to ground. As such, the applications
for high-resistance grounding are somewhat limited to cases with very low
tolerance to higher ground fault currents. A typical case is that of large
turbine generators, which are directly connected to a high voltage transmission
system through a step up transformer. The capacitance current in generator
circuits is usually very low permitting values of ground fault currents
to be as low as 10 A. The low current ensures minimal damage to generator
magnetic core thus avoiding expensive factory repairs. FIG. 6 illustrates
a practical case of grounding the neutral of a generator of this type.

FIG. 6 Grounding of a turbine generator neutral through a high neutral
resistance.
On the other hand, a low-resistance grounding is designed for ground
fault currents of 100 A or more with values of even 1000 A being common.
The value of ground fault current is still far lower than three-phase system
fault currents. This method is most commonly used in industrial systems
and has all the advantages of transient limitation, easy detection and
limiting severe arc or flash damages from happening.
7. Point of grounding
In most three-phase systems, the neutral point at source (a generator
or transformer) is connected to ground. This has the advantage of minimum
potential of the live terminals with reference to ground.
In the case of generators, which are almost always star (wye) connected,
the neutral point is available for grounding. However, in the case of transformer
substations, a neutral may not always be available as the winding may be
delta connected. In such cases, it will be necessary to obtain a virtual
neutral using a device called grounding transformer.
Grounding transformers are generally of two types viz. zig-zag connected
transformer with no secondary winding and a wye-delta transformer. FIG.
7 shows a zig-zag grounding transformer.

FIG. 7 Zig-zag grounding transformer
The transformer primary winding terminals are connected to the system,
which has to be grounded. The neutral point of the transformer is grounded
solidly or through an impedance depending on the type of grounding selected.
Under normal conditions, the transformer behaves like any other transformer
with open circuited secondary (no-load) and draws a small magnetizing current
from the system. The impedance of the transformer to ground fault (zero
sequence) currents is however extremely small. When one of the lines develops
a ground fault, the current is only restricted by the grounding impedance.
Thus, the system behaves virtually in the same manner as any system with
grounded source neutral. FIG. 8 shows this behavior. The ground fault current
flowing in the faulted line divides itself into three equal parts flowing
through each phase winding of the transformer.

FIG. 8 Behavior of a zig-zag connected transformer during a ground fault
The other type of grounding transformer is a wye-delta connected transformer.
The primary winding terminals of the transformer are connected to the system,
which is to be grounded, the neutral of the primary is connected to the
ground and the secondary delta is either kept open or can be connected
to a three-phase three-wire supply system as required (refer to FIG. 9).
This type of transformer too presents a low-impedance path to the flow
of zero sequence currents due to the circulating path offered by the secondary
delta winding. This enables the ground fault current to flow through the
primary and to the ground through the grounding impedance. FIG. 10 illustrates
this action.
British Standard BS: 7671:2000 (IEE Wiring regulations) discusses the
grounding of low-voltage installations in detail and has provided a method
of classifying supply systems based on the type of grounding adopted as
well as the method used to extend the system ground to consumer installations.
The standard also discusses the comparative merits of the different types
of systems for specific applications (refer to Section A for details of
this classification).
8. Other challenges
In the above discussions, we dealt with systems having a single source.
However, when more than one source is involved (such as multiple generators
or a mix of generators and transformers), grounding of neutrals becomes
even more of a challenge. The guiding principles are still the same, viz.
the need for limiting the fault current to safe but easily detectable values
and the prevention of transient over-voltages during a ground fault.

FIG. 9 Star-delta grounding transformer

FIG. 10 Behavior of star-delta grounding transformer during system ground
faults
In the case of power distribution systems with several voltage levels
separated by transformers, it’s necessary to establish neutral grounding
for each individual system, taking into consideration the principles cited
above and the characteristics of each system.
Neutral grounding of electrical systems within large mobile equipment
having their own step down transformers presents further complexities.
These are however beyond the scope of this guide and are not therefore
elaborated.
9. Summary
In this section, we discussed various types of grounding electrical systems
and the considerations that govern the choice. We have also seen how a
virtual neutral point can be established through indirect means using a
grounding transformer. Different types of supply systems based on neutral
wiring practices were reviewed. |