..
1. Introduction
The previous section dealt with the grounding of neutral point of electrical
systems at the source of power. In this section we will learn about the
whys and hows of grounding of electrical equipment at the point of utilization.
The basic objectives of grounding of electrical equipment enclosures are
as follows:
• To reduce electric shock hazards to personnel
• To provide a low-impedance return path for ground fault currents to
the power source so that the occurrence of fault can be sensed by the circuit
protective devices and faulty circuit can be safely isolated
• To minimize fire or explosion hazard by providing a ground path of adequate
rating, matching the let through energy by circuit protective devices
• To provide a path for conducting away leakage current (small currents
flowing through electrical protective insulation around live conductors)
and for accumulated static charges (covered in a later section). We will
review each of these functions in the subsequent paragraphs.
2 Shock hazard
The human body presents a certain amount of resistance
to the flow of electric current.
This however is not a constant value. It depends on factors such as body
weight and the manner in which contact occurs and the parts of the body
that are in contact with the earth. FIG. 1 illustrates this point.
If the flow of current through the human body involves the heart muscles,
it can produce a condition known as fibrillation of the heart denoting
cardiac malfunction. If allowed to continue, this can cause death. The
threshold of time for which a human body can withstand depends on the body
weight and the current flowing through the body. An empirical relation
has been developed to arrive at this value:
Ts= S_B/(I_B)^2

FIG. 1 Resistance of human body to current flow.
where TS is the duration of exposure in seconds (limits of 0.3 and 3
s), IB is the RMS magnitude of current through the body and SB is the empirical
constant.
Using this relation and assuming a normal body weight of 70 kg, it can
be calculated that:
I_B = 0.157 / sqrt T_S
... where IB is the RMS magnitude of current through the body (A) and
TS is the duration of exposure in seconds (decided by the operation of
protective devices).
This value, however, has to be used with care. For example, a considerable
portion of the body resistance is due to the outer skin. Any loss of skin
due to burning in contact with electrical conductors can lower the resistance
and increase the current flow to dangerous values.
In general, two modes of electrical potential application can happen.
The first case is when a person is standing on the ground and touching
an electrically live path. The other is the case of a potential difference
between two points on the ground being applied across the 2 ft with the
distance being about 1 m. Refer FIG. 2, which illustrates these conditions.
Since the human body presents different values of resistance to the flow
of electricity in these two modes, the voltage limits for tolerance of
human body are calculated individually for both cases as follows.

FIG. 2 Modes of application of electric potential
Case 1 Contact with live part by hand
AB FMF = + 0.5( + ) RR RR
where RA is the touch voltage circuit resistance (ohm), RB is the body
resistance (taken as 1000 ohm), RF is self-resistance of each foot to remote
earth in ohms and RMF is the mutual resistance between the feet in ohms.
Case 2 Contact with feet AB F MF = + 2 2 R RR R -
...where RA is the step voltage circuit resistance in ohms, RB is the
body resistance taken as 1000 ohm, RF is the self-resistance of each foot
to remote earth in ohms and RMF is the mutual resistance between feet in
ohms.
The type of contact that normally happens in a building or other consumer
installations is mostly of first mode. The voltage of tolerance in this
mode as calculated in case 1 is called as touch potential. The occurrence
of the second mode of contact is specific to outdoor electrical substations
with structure mounted equipment and therefore is not much of relevance
in our discussions. The voltage value arrived at for case 2 is known as
step potential.
It therefore follows that the design of commercial, industrial and domestic
electrical installations and their grounding methods should be done with
due consideration to touch potential that can arise during abnormal or
fault conditions.
3 Grounding of equipment
Electrical equipment grounding is primarily concerned with connecting
conductive metallic enclosures of the equipment, which are not normally
live to the ground system through conductors known as grounding conductors.
For the grounding to be effective, the fault current (in the event of a
failure of insulation of live parts within the equipment) should flow through
the equipment enclosure to the ground return path without the enclosure
voltage exceeding the touch potential. This is also applicable to other
parts that are normally dead (refer FIG. 3).

FIG. 3 Voltage pattern during ground fault
The touch potential in such a case can be calculated by the application
of Ohm's law: touch G G VIZ =×
...where IG is the maximum ground fault current that is expected to flow
and ZG is the impedance of the ground return path.
Ig is usually determined by the type of system grounding adopted and
the protective devices that are used for fault detection and isolation.
From the above, it will be clear that the impedance of the grounding conductor
between the enclosure and the groundmass should be limited to a value as
low as practically achievable in order to avoid dangerous potential levels
appearing on the enclosures. This will ensure that accidental human contact
with these enclosures won’t result in fatal electrocution or serious injuries.
Another point to note is that in the case of a remote source without direct
connection of metallic ground return path, the ground fault currents tend
to flow through the groundmass. This causes an elevation of groundmass
potential at the receiving end.
Since the touch voltage is between enclosure and local groundmass, it’s
not of relevance as far as human safety is concerned (refer to FIG. 4 for
illustration). This condition is more relevant to three-wire systems in
medium voltage systems where usually metallic ground return paths between
source and receiving equipment are absent. In most low-voltage applications,
this is not likely to be the case. In any case, the point to be remembered
is that the potential rise of the enclosure with reference to local groundmass
is what essentially matters to render the system safe, regardless of other
issues involved.

FIG. 4 Ground potential rise
4 Operation of protective devices
When a fault to an enclosure takes place in electrical equipment, the
return path through the groundmass alone is insufficient to operate the
protective devices such as over-current release or fuses. This is so because
the impedance between the enclosure and the groundmass is usually high
enough to severely restrict the flow of fault currents, which is particularly
true in low-voltage systems that are in common use. In these cases, it’s
imperative that a low-impedance ground return path to the source is available
so that fault current of adequate magnitudes to cause operation of protective
devices is ensured. The grounding conductor fulfills this function of a
low-impedance connection. FIG. 5 illustrates the point.

FIG. 5 Importance of ground return path
5 Thermal capability
It’s essential that the grounding conductor mentioned in the previous
paragraph or any other circuit component, which serves this function, should
be designed to withstand the resulting fault current without developing
excessive temperature or causing sparking at the joints. This will happen
if the joints in the conductor or other bonding connections are improperly
executed. This condition must be true for the magnitude and duration of
the current required for protective devices to operate and isolate the
faulty circuit.
It’s therefore necessary to ensure good quality workmanship in these installations
as otherwise the high temperatures or sparking may cause fires in the premises
where they are installed. Particular care is needed in the case of installations
where hazardous or inflammable materials/mixtures are present.
6 Touch potential during ground faults
As we saw earlier in this section, the touch potential that can develop
on any enclosure is the product of the ground fault current and the impedance
of grounding path. The current value is usually determined by the choice
of neutral grounding method adopted. The impedance is a function of ground
conductor resistance (determined by the conductor size) and reactance (which
depends on the spacing between the phase conductor contributing to the
fault and the ground conductor).
The IEEE:142:1991 discusses this in detail and has provided tables that
illustrate the dependence of touch potential on conductor spacing. FIG.
6 shows the details extracted from this standard. A ground fault current
of 5 kA has been assumed for arriving at these values, which can be reasonably
expected in solidly grounded low voltage systems at the consumer end. Also,
such circuits are not usually provided with sensitive ground fault protection
and rely on over-current releases and fuses, in which case fault currents
of this magnitude are required to operate protective devices within reasonable
time interval.
Spacing (inches) ; Spacing (mm); Touch Voltage (V)

FIG. 6 Relation between touch potential (far end of ground conductor)
and conductor spacing
As can be noticed from FIG. 6, increased spacing between phases and grounding
conductors causes unacceptable levels of touch voltage to appear on the
enclosure of faulted equipment.
7 Induced voltage problem
The spacing between the phases and grounding conductor can also cause
another problem.
The magnetic flux, which is generated when ground fault current flows
through the system can induce voltages in any nearby looped conductor with
which it has a coupling. It’s not necessary that this loop should be in
physical contact with the electrical conductors. Mere magnetic linkage
will be sufficient for this induction. FIG. 7 shows this condition.
The voltage thus induced may not be very high but can drive a high current
if this loop is closed by itself. In the above example, currents of 500
A and an open circuit voltage of 2.5 V can typically appear. The energy
content of this induction will be enough to cause an explosion or fire
if suitable explosive mixtures are present in the immediate environment.
In cases where high earth fault currents are of the order of 50 kA (typically
outdoor substations of solidly grounded type), dangerous potential may
appear across open ends of the loop and can pose an electrical hazard.
This discussion illustrates the need for proper planning for running the
grounding conductors so that touch potential and induced current hazards
are eliminated.

FIG. 7 Example of induced potential
8 Mitigation by multiple ground connection
One way of mitigating the problem is by bonding the ground conductor
at different points to the building structures. This will prevent the voltage
becoming very high by providing multiple earth return paths. But this has
the effect of transferring part of the potential to building structures.
In other words, potential differences may be observed between different
points of the building structures. Also, the partial flow of fault currents
through joints in the structure that are not meant to conduct currents
may cause heating or sparking during faults. This solution has therefore
to be applied with adequate caution.
For example, when reinforced concrete members are used for grounding
purposes, it should be ensured that all reinforcing rods are properly connected
together and joined with exothermic welds to the grounding earth conductor
buried around the building.
Proper attention to detail during the design and construction of high-rise
buildings can result in very low grounding impedances on almost every floor
in a tall building.
9 Mitigation by reduction of conductor spacing
Since the touch potential during faults is dependent on the spacing between
ground return conductor and the phase conductor, it follows that a reduction
of spacing will have the effect of reducing the touch potential. One way
to do this is to run the grounding conductor bundled with the phase conductors.
This will cause the reactance of the ground path to become very low.
Another way is to arrange the ground conductor as a metallic sleeve surrounding
the phase conductor. Besides reducing the reactance of the ground path,
this has the effect of canceling the magnetic flux and preventing any induced
voltages from appearing in external loops as discussed earlier in this
section.
This approach is the basis for using the metal raceway as the ground conductor.
Use of high section rigid steel conduits as grounding conductors has the
effect of reduction of touch potential and elimination of magnetically
induced voltages in external circuits.
The following, however, needs attention:
• Excessive raceway lengths can cause problems by increasing the drop
along the grounding path and by reducing the flow of fault currents.
• Raceway joints should be made without introducing any appreciable electrical
resistance.
• The raceway should have adequate cross-sectional area for carrying ground
fault currents for the length of time required for protection operation.
It’s also possible to have a dedicated grounding conductor running along
with the phase conductors within a metallic raceway, which also acts as
a parallel ground return path which can mitigate some of the problems cited
above.
10 EMI suppression
One of the unplanned benefits of using a metallic conduit as grounding
conductor and as wiring raceway is that any electrical noise emanating
from the electrical system conductors will get suppressed. The conduit
acts like a screen for electromagnetic flux, which get trapped within the
screen and does not radiate outside the enclosure.
This is of particular relevance in modern electrical systems where use
of power semiconductors creates harmonic current flow through the system
as well as line voltage notching, which can act as noise source by radiation
from electrical power conductors. When the conductors supplying power to
such equipment are enclosed within the metallic raceway, such electromagnetic
interference (EMI) automatically gets suppressed.
11 Metal enclosures for grounding conductors
The earlier discussion was about the use of metallic raceway surrounding
the phase conductors as grounding conductors for improved performance.
But the use of a protective metallic sleeve around a grounding conductor
from the service ground point to a grounding electrode presents a different
problem.
These conductors carry current only when there is a ground fault and carry
current one way.
The other part of the current flows in a different circuit remote from
the grounding conductor.
Providing a steel protective sleeve, which is a magnetic material around
this conductor, has the effect of increasing the reactance of the conductor
by a factor of about 40. Take, for example, a coil wound on a former without
core connected to an AC supply.
Now put a magnetic core within the former. You will notice that the current
drops sharply because of the increased inductance. The pipe sleeve behaves
in a similar fashion as the core (refer FIG. 8).
To avoid this problem, it’s necessary to bond the grounding conductor
at both entrance and exit points with each integral section of the metallic
enclosure. This results in reduction of impedance and therefore the voltage
drops. Simultaneously, the metal sleeve also acts as a parallel grounding
conductor and causes the voltage drop to reduce further (refer FIG. 9).

FIG. 8 Coil with and without a core

FIG. 9 Bonding of earth conductor within a pipe sleeve
12 Grounding connections for surge protection equipment
Special care is necessary for conductors that connect surge suppression
equipment ground leads with ground electrodes. When the surge suppressors
act to conduct line surges to ground, a steep fronted current wave passes
through the device to ground. The voltage of the grounding terminal will
depend on the inductance of the grounding conductor, which in turn depends
on its length. For a typical lightning surge with a rate of rise of typically
10 kA/µs, the voltage drop in the length of the grounding conductor is
substantial. The voltage on the terminals of the equipment, which is to
be protected, is the sum of the lightning surge suppressor's breakdown
voltage and the voltage drop in the grounding wire. FIG. 10 illustrates
this principle (a practical example of the importance of this principle
has been explained in Section 10).

FIG. 10 Ground connection of surge suppressor of a transformer.
13 Sensing of ground faults
A sensitive protection for ground faults will use one of the following
approaches:
• In case the power supply source (such as the transformer) is a part
of the system, a CT and relay can be provided in the ground connection
of the neutral of the transformer ( FIG. 11a).
• By a single current transformer enclosing all phase and neutral conductors
(called as core balance or zero sequence CT). Such a transformer detects
the ground fault currents and can operate a sensitive relay ( FIG. 11b).
• By individual current transformer in phase and neutral conductors and
providing a relay in summation circuit ( FIG. 11c).
• Adding special ground fault equipment to the system to sense even low
value of earth fault currents and trip the circuit faster.
Inclusion of the neutral in FIGs. 11b and c is for canceling any unbalance
currents that may flow in the neutral from being sensed as ground faults.

FIG. 11 Sensitive ground fault protection connections
14 Equipotential bonding
Equipotential bonding is essentially an electrical connection maintaining
various exposed conductive parts and extraneous conductive parts at substantially
the same potential. An earthed equipotential zone is one within which exposed
conductive parts and extraneous conductive parts are maintained at substantially
the same potential by bonding, such as that, under fault conditions, the
difference in potential between simultaneously accessible exposed and extraneous
conductive parts won’t cause electric shock.
Bonding is the practice of connecting all accessible metalwork - whether
associated with the electrical installation (known as exposed metalwork)
or not (extraneous metalwork) - to the system earth. In a building, there
are typically a number of services other than electrical supply that employ
metallic connections in their design. These include water piping, gas piping,
HVAC ducting, and so on. A building may also contain steel structures in
its construction. We have seen earlier in this section that when an earth
fault takes place in an installation, the external conducting surfaces
of the installation and the earth mass in the vicinity may attain higher
potential with reference to the source earth. There is thus a possibility
that a dangerous potential may develop between the conducting parts of
non-electrical systems including building structures and the external conducting
parts of electrical installations as well as the surrounding earth. This
may give rise to undesirable current flow through paths that are not normally
designed to carry current (such as joints in building structures) and also
cause hazardous situations of indirect shock. It’s therefore necessary
that all such parts are bonded to the electrical service earth point of
the building to ensure safety of occupants. This is called equipotential
bonding.
There are two aspects to equipotential bonding: the main bonding where
services enter the building and supplementary bonding within rooms, particularly
kitchens and bathrooms.
Main bonding should interconnect the incoming gas, water and electricity
service where these are metallic but can be omitted where the services
are run in plastic, as is frequently the case nowadays. Internally, bonding
should link any items, which are likely to be at earth potential or which
may become live in the event of a fault and which are sufficiently large
that they can contact a significant part of the body or can be gripped.
Small parts, other than those likely to be gripped, are ignored because
the instinctive reaction to a shock is muscular contraction, which will
break the circuit. In each electrical installation, main equipotential
bonding conductors (earthing wires) are required to connect to the main
earthing terminal for the installation of the following:
- • Metal water service pipes
- • Metal gas installation pipes
- • Other metal service pipes and ducting
- • Metal central heating and air-conditioning systems
- • Exposed metal structural parts of the building
- • Lightning protection systems.
It’s important to note that the reference above is always to metal pipes.
If the pipes are made of plastic, they need not be main bonded. If the
incoming pipes are made of plastic but the pipes within the electrical
installation are made of metal, the main bonding must be carried out, the
bonding being applied on the customer side of any meter, main stopcock
or insulating insert and of course to the metal pipes of the installation.
Such bonding is also necessary between the earth conductors of electrical
systems and those of separately derived computer power supply systems,
communication, signal and data systems and lightning protection earthing
of a building. Many equipment failures in sensitive computing and communication
equipment are attributable to the insistence of the vendors to keep them
separated from the electrical service earth. Besides equipment failures,
such a practice also poses safety hazards particularly when lightning discharges
take place in the vicinity. In such cases, large potential difference can
arise for very short periods between metal parts of different services
unless they are properly bonded. Some of the case studies in a later section
deal with this issue.
If the incoming services are made of plastic and the piping within the
building is of plastic, then no main bonding is required. If some of the
services are of metal and some are plastic, then those that are of metal
must be main bonded. Supplementary or additional equipotential bonding
(earthing) is required in locations of increased shock risk. In domestic
premises, the locations identified as having this increased shock risk
are rooms containing a bath or shower (bathrooms) and in the areas surrounding
swimming pools.
There is no specific requirement to carry out supplementary bonding in
domestic kitchens, washrooms and lavatories that don’t have a bath or shower.
That is not to say that supplementary bonding in a kitchen or washroom
is wrong but it’s not necessary. For plastic pipe installation within a
bathroom, the plastic pipes don’t require supplementary bonding, and metal
fittings attached to these plastic pipes also would not require supplementary
bonding. However, electrical equipment still does require to be bonded
and if an electric shower or radiant heater is fitted, they will require
supplementary bonding as well.
Supplementary bonding is carried out to the earth terminal of equipment
within the bathroom with exposed conductive part. A supplementary bond
is not run back to the main earth. Metal window frames are not required
to be supplementary bonded unless they are electrically connected to the
metallic structure of the building. Metal baths supplied by metal pipes
don’t require supplementary bonding if all the pipes are bonded and there
is no other connection of the bath to earth. All bonding connections must
be accessible and labeled: SAFETY OF ELECTRICAL CONNECTION - DO NOT REMOVE.
15 Summary
In this section, we learnt about the basic issues of electric shock hazards.
We reviewed the need for providing grounding connections to electrical
equipment and the methods adopted for grounding. We discussed the ways
and means of limiting the potential on equipment enclosures to safe values
by proper ground connections. We also learnt how sensitive earth fault
protection can be provided and where such protection is likely to be required.
Information regarding grounding of substations and equipotential bonding
of residential buildings was also covered. The salient provisions of various
international codes relating to grounding and analysis of grounding behavior
in MV/LV systems are discussed in sect. A and they may be referred for
additional information.
|