.
1 Introduction
Lightning is one of the most widely studied and documented natural phenomena.
It’s also one of the main causes of transient over-voltages in electrical
systems. A proper understanding of lightning is essential for planning
protection against lightning strikes so that no untoward damage is caused
to buildings and electrical installations.
A lot of research has been done over a number of years worldwide and several
publications as well as national and international standards have evolved
which give us a good insight into this phenomenon. Some of these are:
• AS 1768: 1991 Australian standard on lightning protection
• ANSI/NFPA 780 National lightning protection code
• IEEE 142: 1991 IEEE green guide ( Section 3)
• IEC 1024:1993 Protection of structures against lightning.
Lightning is the sudden draining of charge built up in low-cloud systems.
It may involve another cloud system (which is not of much interest to us
in this guide) or ground (which is). The flow of charge creates a steep
fronted current waveform lasting for several tens of microseconds. The
flow is more usually that of negative charges though at times it may involve
positive charge flow too. The latter are generally of lower magnitude and
hence not critical to this discussion. FIG. 1 shows a typical lightning
waveform.
Some of the parameters of interest to us are:
• Peak current I usually expressed in kiloamperes
• Rate of rise of current dI/dT in kiloamperes per microsecond
• Time to crest TCR in microseconds
• Time to fall to half of peak value TH. As the rate of rise is not uniform
throughout, this value is further expressed as dI/dT (Max), dI/dT (10/90%)
and dI/dT (30/90%). dI/dT (Max) is the maximum value of slope in the rise
curve, dI/dT (10/90%) is the average slope between 10% of peak current
and 90% of peak current and so on.

FIG. 1 Typical waveform of lightning
The occurrence of lightning flash starts with a buildup of charge in
a cloud system close to the ground. This charge is usually of the order
of several million volts and usually of negative polarity at the bottom.
Though the exact mechanism of charge separation is not clear, observations
indicate that the ice particles in the top portion of the cloud are positively
charged whereas the heavier water particles in the bottom portion of the
cloud carry a negative charge. FIG. 2 shows the charge separation in a
cloud and the corresponding induced charges in the ground. The movement
of clouds causes corresponding movement of positive charges on the ground.
This is observable as current flow in metallic pathways such as pipelines
on the ground.
The high electrical field causes ionization of air and creates a conducting
path. This usually happens near the cloud and the ionized path is called
the downward leader. The leader precedes in steps of 20-30 m toward the
ground, each step forming further ionization of the subsequent step. Simultaneously,
from the high points or structures on the ground upward leaders of positive
charges start forming. The interception of downward leaders and upward
leaders completes the conducting path between the cloud and the ground
and results in a lightning strike (see FIG. 3). The lightning flash along
the ionized path causes a very high peak of current amounting to several
kilo amperes and dissipates its energy in the form of heat (temperatures
up to 20 000°C for a few microseconds), sound and electromagnetic waves
(light, magnetic fields and radio waves).

FIG. 2 Charge separation in a cloud and induced charges in the ground

FIG. 3 Lightning strike initiation
Each lightning strike consists of several component parts (each is a
current wave called a stroke). The first current wave with a relatively
lower dI/dT rate but higher in magnitude and several more (on an average
3) of much higher dI/dT but lower peak currents. FIG. 4 shows a typical
lightning discharge.

FIG. 4 A typical lightning discharge with multiple wave components (strokes)
Like any typical natural phenomena, lightning strikes are not all identical
but vary widely in their parameters. The values of these parameters are
therefore defined in a probabilistic format. The tables shown in FIGs.
5 and 6 are examples of such variation. FIG. 5 shows a table for peak lightning
current. FIG. 6 shows the maximum and average rate of rise of lightning
current.

FIG. 5 Peak lightning current values
2 Incidence of lightning
Lightning depends on both atmospheric and geographical factors. It’s
usually associated with areas having convection rainfall. It requires presence
of high moisture levels in air and high surface temperatures on ground.
For example, the incidence of lightning is very high in Florida whereas
in colder locations such as Canada where moisture levels in atmosphere
are equally high are much less prone to lightning. Since the protection
to be given to buildings is a function of the probability of lightning
strikes, the frequency of lightning occurrence has been extensively studied
and the results are published in the form of annual isokeraunic maps for
different world regions. These are contour maps, which show the mean annual
thunderstorm days of the region involved.
A thunderstorm day for this purpose is defined as one when thunder is
heard at the point where it’s measured. This obviously cannot indicate
whether it’s a result of inter-cloud or cloud to ground discharge. It does
also show the frequency/number of instances or severity of cloud to ground
strikes. Further studies are under way to gather such data and may result
in modifications to the present methods of lightning risk assessment.
The isokeraunic map for Australia and New Zealand as well as Continental
USA and Canada are shown in FIGs. 7a-e.
FIG. 6 Maximum and average rate of rise of lightning current

FIG. 7a Isokeraunic map of Australia

FIG. 7b Isokeraunic map of New Zealand

FIG. 7c Isokeraunic map of USA

FIG. 7d Isokeraunic map of Canada

FIG. 7e Isokeraunic map of the UK
Methods have been developed to compute the ground flash density (flashes/
km^2 /year) from the average thunderstorm days. Table in FIG. 8 gives the
relationship between these parameters.
3 Probability of lightning strike
The probability of lightning strike depends on two factors: the incidence
of lightning strikes in the geographical area where the structure is situated
and the attractive area offered by the structure for lightning. The attractive
area can be defined as the horizontal area within which a downward leader
will be intercepted by an upward leader originating from the structure.
FIG. 9 shows the attractive area for a lightning mast. The attractive area
in turn depends on the attractive radius RA (shown in FIG. 9). If the downward
leader of a lightning comes anywhere within the sphere formed by the attractive
radius with the top of the mast as center it will strike the mast.

FIG. 8 Relationship between thunderstorm days and ground f lash density

FIG. 9 Attractive radius of a lightning mast An empirical formula for
the attractive radius is:
0.6 0.74 A 0.84 R hI =××
Where RA is the attractive radius in meters, h is the height of the lighting
mast in meters and I is the peak lightning current in kiloamperes.
For a horizontal conductor (such as the shield wire provided on an overhead
electrical line) the attractive distance LA is given by the formula:
0.6 0.74 A 0.67 LhI =××
Where LA
... is the distance of attraction on either side of the conductor in meters,
h is the height of the conductor from ground in meters and I is the peak
current of lightning in kiloamperes.
The number of lightning strikes that a structure will attract in 1 year
can be arrived by multiplying the ground flash density (in flashes/km^2
/year) with the attractive area expressed in km^2.
4 Method of lightning protection
Lightning protection to any building or structure consists of providing
a safe low impedance conducting path for flow of lightning discharge currents
to ground without allowing them to flow through the building structures.
In practical terms, such protection consists of an air termination, down
conductors and ground electrodes. A lightning mast independent of the structure
but near enough to divert any lightning occurring in the vicinity is one
example of protection. FIG. 10 illustrates how a nearby mast protects a
building. The protection offered may not be complete if the attractive
radius of the building to lightning extends well beyond that of the mast.
In such a case, it’s possible that some of the strikes may hit the building
rather than the mast.

FIG. 10 Building protected by a nearby mast
Whether a structure gets adequate protection from a lightning mast can
be verified by using the principle of cone of protection. FIG. 11 illustrates
this principle. The angle A can vary between 30 and 60 º depending on the
degree of lightning protection desired for the structure (lower values
for higher degree of protection).

FIG. 11 Example of the cone of protection principle
This concept is somewhat outdated and other better methods have been
evolved to more accurately predict the protection offered. One such method
is the rolling sphere principle of protection. FIG. 12 illustrates the
protection offered by a building's lightning protection system to adjacent
structures.

FIG. 12 Rolling sphere method of protection
A sphere is rolled over the protecting structure and the shaded areas
which the sphere cannot touch are within the protection zone. The radius
of the sphere can vary between 20 and 60 m depending on the degree of protection
required. The standard protection will consider a radius of 45 m and increased
degree of protection can be obtained by reduction of the radius (refer
FIG. 13).
===
Protection Level -- Radius of Sphere (m)

FIG. 13 Rolling sphere radius for different protection levels
===
Protection levels shown in FIG. 13 are in descending order of importance
of the structure to be covered (protection level I to be applied for structures
requiring the greatest protection, and so on). Since all buildings cannot
be protected by a free standing mast, the more usual approach is to have
the conductors placed on the building itself (called as air terminations)
and connect them to the ground through down conductors. The air terminations
can optionally be vertical spikes placed on the top periphery of the building.
These air terminations can be connected by a flat conductor run on the
roof thereby offering multiple paths for the lightning current to flow
to ground. The down conductors are connected to dedicated ground electrodes
to offer a short conducting path to ground. FIG. 14 illustrates this arrangement.

FIG. 14 Typical lightning protection to a building
Lightning behaves like a current source. In other words, the flow of
current is independent of the circuit impedance. If the current path to
ground has high-impedance elements, the lightning current, which is of
the order of several kiloamperes as we saw earlier, produces a very high
voltage drop. This voltage appearing on the conducting elements can cause
secondary flash to nearby earthed objects. It can also cause damage to
building structures by forcing a path through non-conducting building elements.
This explains why the lightning conductors should be of as low impedance
or in other words as low a length as possible. FIG. 15 illustrates the
example of side flashes.

FIG. 15 How side flashes are caused
5 Planning for lightning protection
The protection to be given for a structure or facility against lightning
strikes is based on the probability of lightning strike (as detailed in
the previous section) and the extent of risk of damage or disruption that
a lightning strike can cause. Based on the latter criterion, structures
can be divided into various classes in ascending order of protection requirement.
Class 1: Structures, which need very little or no additional protection
except connecting them to an effective ground electrode, come under this
category. These are all-metal structures, buildings with metallic roofing,
side cladding and metallic frame work, stand-alone metallic masts, etc.
Class 2: Structures that have a metallic roof, side cladding and non-conductive
framework are in this category. Protection to these structures is provided
by down conductors bonded to the roof and side members and connected to
ground electrodes.
Class 3: These include metallic frame buildings with non-metallic roof
and side cladding. In this case, air terminations on the top of the building
and on other non-conducting surfaces connected to the metal frame of the
building are required to protect the insulating surfaces from being punctured
by lightning.
Class 4: This class includes completely non-metallic structures such as
buildings and tall chimneys/stacks constructed of reinforced concrete or
masonry. These structures need extensive protection using air terminations,
down conductors and grounding electrodes.
An example of such protection is shown in FIG. 16.

FIG. 16 Example of lightning protection of a class 4 structure
Class 5: Buildings of historic or public importance or those containing
valuable materials, places where a large number of people can gather at
a time and public utilities such as power plants, water works, etc. come
in this category and need utmost attention while planning protection.
6 Improvements to lightning protection
The protection to buildings and structures can be improved by better
methods of prediction and by the use of active protection systems. We will
cover them briefly below.
In 1979, Eriksson presented an improved model, which allows for the intensification
of ambient electric field created by a grounded structure. Eriksson's work
was a fundamental step forward in lightning protection design, since it
supported the field observations that the majority of lightning flashes
terminate on the corners and nearby edges and other sharp features of unprotected
structures, i.e. the points of highest electric field intensification.
The ERICO scientists and engineers extended Eriksson's basic model for
application to practical structures back in the late 1980s. This has been
done through computer modeling of electric fields around a wide range of
3D structures and by application of the concept of 'competing features'
to determine whether a structure is protected. This relatively new method
has been known worldwide as the collection volume method (CVM) (refer to
FIG. 17).

FIG. 17 Collection volume method
The CVM takes the physical criteria for air breakdown, together with
a knowledge of the electric field intensification created by different
points on a structure and uses this information to provide the optimum
lightning protection system for a structure, i.e. the most efficient protection
design for the required protection level. Using the modern risk management
approach, the CVM output depends on user-selected protection levels as
per the previous rolling sphere method.
Active protection systems are also being offered by several vendors and
are claimed to offer a higher degree of protection compared to the passive
systems comprising air terminations and down-comers described earlier.
The efficacy of many of these systems is however to be proven under actual
installation conditions. The basic principle behind these systems is as
follows. The active air terminations provided in these systems (which are
vertical rods with an active component at their tip) generate a high electrical
field as soon as a downward leader from a cloud starts toward the ground
and immediately cause an upward leader to emanate from the air termination.
Though a normal air termination also behaves in roughly the same fashion,
the active protection systems react much faster. As a result the upward
leader from the active air termination reaches out much higher resulting
in the lightning strike to be invariably directed to the ground through
the protection system.
7 Factors governing decision whether or not to protect
Standard AS 1768 provides clear guidelines to take a decision to provide
or not to provide lightning protection to a building or structure based
on an assessment of risk involved.
The assessment is done in terms of the likelihood of the structure being
struck and the consequences of any such strike. The use of the structure,
the nature of its construction, the value of the contents and the prevalence
of thunderstorms in the area can all be considered in making the assessment.
A decision to provide lightning protection may, however, be taken without
any risk assessment, For example, where there is a desire that there should
be no risk to a structure at all.
Examples of such structures are:
- • Those in or near which large numbers of persons congregate
- • Those concerned with the maintenance of essential public services
- • Those in areas where lightning is prevalent
- • Very tall or isolated structures and
- • Structures of historic or cultural importance.
Where it’s thought that the consequential effects will be small and that
the effect of a lightning flash will most probably be merely slight damage
to the structure, it may be economic not to incur the cost of protection
but to accept the risk. Even then, it’s better to make an assessment so
as to give some idea of the magnitude of the risk that is being taken.
The need to protect electronic equipment and to protect persons against
potential differences associated with metallic services increases with
the building area. In such cases even though the construction of the structure
does not warrant protection, appropriate measures must be taken to avoid
risk to persons and equipment.
The standard also stipulates that any structure which is entirely within
a zone protected by an adjacent object or objects (whether protected or
not) should be deemed to be protected, that is no separate protection is
necessary for such structures.
The standard defines a set of five indices:
- 1. Index A type of structure
- 2. Index B type of construction
- 3. Index C height of structure
- 4. Index D situation (location)
- 5. Index E lightning prevalence (thunderstorm days/year).
The sum of these indices (R) can be used to determine the need for protection.
For more details, the relevant standard may be referred.
8 Effect of lightning strike on electrical lines
The foregoing discussion concentrated on the principles of lightning
strikes and how their effects can be mitigated. However, lightning strikes
on electrical lines or substations are those that cause problems in the
distribution network which come right into our residences and offices.
A full discussion on the protection of transmission and distribution lines
from direct lightning strikes is beyond the scope of this guide. We will,
however, briefly touch upon this aspect further.
A direct strike on a conductor of a power line causes extremely high voltage
pulses at the strike point, which are propagated as traveling waves in
either direction from the point of strike. The crest of the pulse can be
calculated as:
= VI Z ×
Where V is the crest voltage, I is the peak lightning current and Z is
the impedance seen by the pulse along the direction of travel.
Impedance Z is equal to half the surge impedance of the line when struck
at mid-point and can be approximately as much as 150 ohm. Thus for a peak
current of 40 kA, the voltage of the pulse can be as high as 6000 kV. Since
the basic insulation level of most systems is much lower than this value,
it’s clear that such a pulse will cause failure of insulating components
along the line. It’s therefore necessary that no direct strike must be
permitted on the overhead power line's phase conductors. This is achieved
by stringing one or more shield wires along the phase conductors sufficiently
above them so that the shield wires attract direct strikes and not the
phase conductors. The shield wire is earthed at each transmission tower
and thus the lightning current safely passes into the groundmass.
The clearance between the phase conductors and the shield wire must be
selected so that air space between them does not breakdown by the high
impulse voltage generated in the shield wires. This is easily achievable
in systems of 66 kV and higher.
Even when protected in the above manner, the flow of the pulse of lightning
current in the shield wire causes an induced voltage pulse in the phase
conductors. These being much smaller in value than the direct pulse safely
pass along the line without causing any insulation failure. To protect
the equipment at the termination point of the overhead lines (such as circuit
breakers, transformers, measuring devices, etc.), lightning arrestors are
provided at the point of termination. These arrestors absorb any surges
in the line and prevent them from traveling into the substation equipment.
These arrestors are essentially non-linear resistors in a porcelain housing
which at normal voltages present a very high resistance. They are designed
to break down at voltages above the highest system operating voltage (but
lower than the basic insulation level of the system) thereby becoming good
conductors and pass the energy of the lightning impulse to the ground.
Once the voltage comes down (after the discharge of the pulse is over)
the arrestors return to their original high-impedance state. The arrestors
are placed on structures and their line terminals connected to each phase
of the line. The other end of the arrestor (ground terminal) is connected
to the substation grounding system through short ground conductors of adequate
cross-sectional area. Arrestors can also be optionally provided with surge
counters for the purpose of monitoring their action.
9 Summary
In this section, we have reviewed the phenomenon of lightning, their
effects on the installations in the ground. The probability of lightning
strikes based on the ground geography and the configuration of the grounding
installation was analyzed. We also went through the methods adopted for
safeguarding the installations from the effects of a strike. The various
classes of structures and how these are to be protected were also covered.
The effect of lightning on electrical installations and the practices for
ensuring their safety were also described.
|