<< cont. from prev.
MAINTENANCE IN SERVICE (cont.)
The second case-study might be considered less of a success in that it did
not enable a fault to be pinpointed and repairs made. This is partly because
there were a number of relatively minor faults taking place concurrently and
partly because operations and maintenance staff had carried out a number of
degasifications of the oil. Maintenance staff can sometimes be faced with a
dilemma when transformer dissolved gas levels are increasing. The concern is
that these might reach a level at which free gas will be released leading to
Buchholz relay operation. To avoid this the strategy is to treat the oil in
order to lower dissolved gas levels. This procedure unfortunately greatly confuses
efforts at fault diagnosis, since although gas-in-oil levels are reduced, the
gas in the insulation remains at a high level. This then diffuses into the
oil until an equilibrium is reached, thus increasing gas-in-oil levels, but
at rates which are not related to the fault. When attempting to obtain a diagnosis,
therefore, it is always preferable not to treat the oil.

FIG. 125 Generator transformer number 1 dissolved gas levels on initial
commissioning
 Table 11 Levels of dissolved hydrocarbon gases (parts per million) in generator
transformer 1 oil samples against time of sampling and values of gas ratios
as were calculated at the time and as Roger ratios.

FIG. 126 Case study number 1 Generator transformer number 1 dissolved
gas levels after repair
The transformer was a 19.5/300 kV generator transformer and the dissolved
gas levels first gave cause for concern when the transformer had been in service
for about 6 years and continued for a further period of some 14 years until
it was finally removed from service for scrap following Buchholz relay operation.
Table 12 gives the dissolved gas levels over this 14 year period and indicates
the timing of oil treatments. Rogers Ratios are also included. During the final
3 years of service the generator voltage was restricted to 18.7 kV due to machine
problems and it will be noted that during this period dissolved gas levels
were seen to stabilize. Throughout the period in service the generator AVR
was known to exhibit a control problem which resulted in genera tor voltage
frequently exceeding 19.5 kV. It was considered that some of the transformer
problems were due to overfluxing resulting from these periods of overvoltage
and this was probably confirmed by the reduction in gas evolution following
the reduction in machine operating voltage. It will be seen that there is no
clear pattern to the Rogers Ratios. Because of the complex gas evolution history
of this transformer and the large amount of monitoring data which had been
amassed it was decided that it might well be instructive to dismantle it for
as detailed an inspection as possible before totally scrapping it. The inspection
revealed that there had been several faults, some of which had probably developed
earlier than others and some which probably owed their origin to the overfluxing.
Among the faults identified were:
• Arcing of winding clamping-pressure adjusting screws.
• Arcing of a connection to a winding stress-shield.
• Burning of core plates at their edges consistent with severe circulating
currents.
• Indication of overheating of core frames and adjacent core frame insulation.
It was considered possible that these latter two faults owed some of their
existence to the overfluxing incidents.
This latter case study demonstrates some of the difficulties which can be
experienced on some occasions when attempting to draw meaningful conclusions
from d.g.a. results. Dissolved gas analysis can, at best, serve to alert an
operator to the existence of a problem. There can then often be many additional
problems such as whether to take the unit out of service in an effort to locate
the fault by means of an in-tank inspection and, even if this decision has
been taken, should the fault be buried deep within windings it will not be
located from such an inspection. The next problem is then whether to go further
and take the unit completely out of commission for dismantling. Most operators
will , rightly, fight shy of this decision.
 Table 12 Case study number 2. Dissolved gas levels and Rogers ratios for
genera tor transformer over period 1969-1983. Shaded bands indicate data from
samples taken immediately after degasification of oil.
Gas monitors
Very occasionally it will be the case that a serious fault will be detected
of a considerable magnitude. Often, despite the seriousness, there will be
pressures to retain the transformer in service, perhaps until an approaching
out age, or perhaps until a spare unit can be brought from another location.
In these circumstances very frequent sampling will be called for and it is
possible that it will be economic to install an on-line gas monitor. Such equipment
can be connected into the oil circuit and arranged to take and analyze samples
at intervals as frequently as hourly. An alarm level, either for a particular
gas, or for total gas content in the sample, can be set to indicate at a remote
location should this alarm level be exceeded.
An early device of this type was developed by CEGB in conjunction with Signal
Instruments of Camberley, Surrey. For some years it continued to be manufactured
and marketed by Signal Instruments, although being quite costly and not, therefore,
justifiable except in special circumstances, there was a very limited market
so that production was discontinued in the early 1990s.
A more economical on-line device was the Hydran continuous gas monitor which
was also developed in conjunction with CEGB. This operates on the principle
that hydrogen is produced whenever there is a fault (see FIG. 122). It is
therefore designed only to detect the presence of hydrogen and can be set to
alarm as soon as this is found in a continuous sample.
The disadvantage of this device is that it simply alarms at the presence of
a particular gas. As should be evident from the above, it is not so much the
presence of gas, or gases, which are indicative of a fault so much as a sudden
change in the status quo. It is understood that the most modern versions of
the Hydran can, in fact, be set to ignore a steady situation and only raise
the alarm should a step-change occur.
Certainly there are occasions when it can be beneficial to monitor a transformer
with some such device which is able to warn of a very rapidly developing fault.
Whenever a manual system of sampling is instituted there is a limit to the
frequency at which this can be carried out. It is impractical to operate a
system of taking routine samples more frequently than, say, every one or 2
months and a lot can happen in this interval. It is understood that the National
Grid Company in the UK now specifies that all new transformers supplied for
the 400 and 275 kV grid systems are provided with provision for installation
of on-line dissolved gas monitoring devices.
Another proposal worthy of consideration and requiring the facility for easy
connection of an on-line gas monitor, is that all newly commissioned EHV transformers
should be monitored on-line for at least the first 3 months of service.
Degradation of cellulose
Although by the late 1970s considerable progress and many successes had been
achieved in CEGB using the dissolved gas analysis techniques described, one
or two major catastrophic failures which had not been predicted had occurred
and these underlined one of the weaknesses of the dissolved gas analysis approach.
One of the problems is that at very low levels of overheating, which are nonetheless
serious enough to result in significant shortening of life expectancy, the
volumes of hydrocarbon gases produced are so low that it is difficult to measure
their concentration in the oil with any accuracy.
==========
 FIG. 127 Liquid chromatogram showing separation of paper degradation products
extracted from oil:
Column C18 alkane bonded Peaks to silica 1 2-furoic acid Particle size: 10
µm 2 solvent front Length 300 mm 3 5-hydroxy methyl Mobile phase: 20% 2-furfuraldehyde
Methanol in water to 100% 4 2-furfuryl alcohol methanol 5 2-furfuraldehyde
Flow rate: 0.025 ml/s 6 2-acetyl furan Detector: UV216 nm 7 5-methyl-2-furfuraldehyde
Sample: 15 µl methanol 8 oil compounds soluble extract in methanol
==========
It was therefore felt that a more precise and sensitive method of detecting
paper degradation was required. It was against this background that the work
described below was initiated. The information is taken from a paper presented
to CIGRE at its August/September meeting in 1984 by Messrs P.J Burton, J. Graham,
A.C Hall, J.A Laver and A.J Oliver of CEGB [6.9]. The method developed is based
on the analysis of the oil for compounds that are produced exclusively by thermal
degradation of paper at temperatures as low as 110ºC. The intention was that
the procedure should be used in conjunction with dissolved gas analysis rather
than independently. That is, reliance should be placed on normal d.g.a. techniques
to raise the alarm that a possible fault condition exists, but the new technique
should then be applied to obtain more information regarding the nature and
magnitude of the fault.
Oil samples are taken as for the d.g.a. procedure but are then mixed with
methanol. A certain quantity of the compounds sought then become dissolved
in the methanol at concentrations determined by the equilibrium levels with
the oil (a similar process to the oil/water/paper equilibrium situation previously
described) The methanol and its solutes are then injected into a high performance
liquid chromatograph (HPLC) for separation and measurement of the individual
compounds. A typical chromatogram is shown in FIG. 127.
The main reason for using the methanol extraction stage is to avoid those
constituents of the oil which would crowd the chromatograph making the detection
of the compounds being investigated more difficult.
The paper degradation products identified are also listed in FIG. 127 Of
these compounds, 2-furfuraldehyde is the most common product detected from
transformers in service.
Following the development of this method many samples of oil from transformers
in service have been analyzed for furfuraldehyde. In one particular 22/400
kV generator transformer, it was noted that the dissolved ethane and methane
concentrations were increasing fairly rapidly indicating that an over heating
fault existed having a temperature within the range 150-200ºC. The furfuraldehyde
concentration also increased over the same period of 16 weeks from about 0.7
to 1.7 mg/l suggesting that paper as well as oil was being over heated. The
transformer eventually failed.
Investigations into the failure revealed that the A and B phase windings were
loose, probably as a result of a fault on the transmission system and that
the transformer tripped due to an interturn fault on the B phase LV winding.
Paper insulation had been overheated confirming the conclusions drawn from
the furfuraldehyde measurements.
Confidence is now growing in the use of this method of detecting paper degradation.
However, there are also problems similar to those identified with d.g.a. There
is no such thing as a norm for furfuraldehyde level in a healthy transformer,
so that it is not possible, as some authorities might have hoped, to carry
out general measurements of furfuraldehyde levels throughout transformer populations
to identify those for which the insulation is prematurely ageing. There is
no reliable way of differentiating between a large mass of paper which is just
slightly degraded and a localized area for which degradation is seriously advanced.
It is also the case that if a short term overload causes overheating and significant
ageing, with associated furfuraldehyde production, and then this is followed
by a period of normal loading without over heating, the furfuraldehyde will
be absorbed into the mass of the paper, so that the levels in the oil will
appear little different from normal. Once again, as in the case of d.g.a. it
is observation over a period and the detection of step changes which can be
regarded as indicative of a fault condition.
Dissolved gas analysis during works testing
It should be recognized, of course, that the value of d.g.a. as a diagnostic
tool need not be restricted to transformers that are in service. D.g.a. can
serve a very useful function during works testing.
Utilities are becoming increasingly conscious of the fact that a few hours
in works testing is a very limited time in which to demonstrate that a large
transformer will be suitable for thirty or more years satisfactory service.
In addition specifications are tending to allow higher operating temperatures
and, although these, in theory, still allow margins above the average values
which can be measured on test for hot spots, the customer has no guarantees
that there will not be hot spots which exceed this allowance. There is also
a tendency for transformer manufacturers to shorten the overall times for temperature
rise tests by reducing the cooling of a forced-cooled unit during the initial
phase of the test, thereby reducing further the likelihood of some faults being
brought to light. As a counter to this many users are specifying that the temperature
rise test, or perhaps, more correctly, load-current run, should be continued
for 24 hours. On this timescale it is possible to obtain meaningful d.g.a.
figures from oil samples taken before and after this load-current run.
It is not normally considered practicable to set any acceptance/rejection
level on d.g.a. figures but analysis of the oil samples will not only clearly
show the presence of any more significant fault, but can also be expected to
reveal the presence of modest overheating of the insulation which would affect
the transformers overall life expectancy.
Of course, one criticism of a short-circuit temperature rise test is that
the core flux-density is low and consequently leakage fluxes which could give
rise to overheating in service will be very much reduced. The CEGB response
to this was to specify a prolonged overvoltage run, equivalent to about 8.3
percent overfluxing for 3 hours. This was considered long enough to produce
detectable gas levels in the oil should there be any significant overheating
resulting from leakage fluxes.

Table 13 Dissolved gas analysis used during testing: case study number 1
from paper presented at IEEE Summer Meeting, 1981
Many manufacturers, of course, recognize the benefits of identifying incipient
faults during works testing rather than having these possibly dam age their
reputations by coming to light in service and so advocate the use of d.g.a.
as an aid to assessing performance during works tests. The two case studies
which follow were described in a paper presented to the IEEE Power Engineering
Society summer meeting in July, 1981, by the Westinghouse Electric Corporation
[10]. Both units tested were of the shell type.
The first case was a three-phase transformer with on-load tapchanger. Table 13 shows d.g.a. results at the end of the factory temperature rise test.
It is assumed that an oil sample would also have been tested before the temperature
rise test but no figures are given. Being a new transformer newly filled and
processed it must be assumed that the initial gas levels were very low. Even
without taking ratios it is clear from the ethylene level that severe overheating
is taking place. In addition, the presence of any acetylene in a new transformer
should always be regarded as indicative of a fault. The paper reports that
investigation revealed the overheating to be due to the effect of leakage fluxes.
After taking corrective measures a repeat of the temperature rise test showed
that the problem had been resolved.
The second reported case was that of a furnace transformer with a very high-LV
rated current. The LV leads and connections were made from large section copper
bar with bolted joints. Table 14 shows the d.g.a. results following the temperature
rise test. Hydrocarbon gas levels are, in reality, quite modest. It is very
unusual to find no hydrogen present at all, however, once again, in a newly
processed transformer none of the gas levels should be expected to exceed a
few parts per million. Certainly the methane and ethane figures must be taken
seriously, but the very low ethylene suggests that on this occasion any overheating
is quite modest. The paper reports that the tightness of all bolted joints
was checked and although none were found to be loose, it proved possible to
tighten some by a further quarter to half turn. A thorough inspection of the
transformer revealed no other fault. That the source of the problem had indeed
been found was proved by repeating the temperature rise test without the production
of any hydrocarbon gases.

Table 14 Dissolved gas analysis during works testing: case study number
2 from paper presented at IEEE Summer Meeting, 1981
 Table 15 IEEE table of dissolved gas concentrations to enable an assessment
to be made of a gassing condition.
Establishment of norms
Most authorities experienced in the use of d.g.a. for hydrocarbon gases and
for cellulose degradation products, are emphatic in the view that it is not
possible to identify 'norms' for healthy transformers for the reasons given
above and that it is change in the status quo which is the clearest indication
of a transformer fault. However, many transformer users feel that there ought
to be norms and there are authorities who have endeavored to provide these.
The American IEEE Standard C57.104-1991, Guide for the interpretation of gases
generated in oil-immersed transformers, infers that in operation all transformers
will have norms appropriate to their age and duty in so far as detection of
a fault first requires the determination that an abnormality exists. This is
akin to looking for a step-change in d.g.a. levels as described above, except
that the document is aiming to identify, in the absence of a d.g.a. history
for a particular transformer, what dissolved gas levels represent the status
quo.
The above IEEE Standard provides values for norms in relation to the total
dissolved combustible gas content (TDCG) for the transformers and these are
set out in Table 15. As will be seen from the table the values of combustible
gases enable the transformer to be placed into conditions 1-4 which are set
out in Table 16. The document states that the values are consensus values
based on the experiences of many companies. Only condition 1 is regarded as
satisfactory, but it will be recognized that even a condition 1 transformer
could, according to the table, be expected to contain up to 35 p.p.m. of acetylene.
The document goes on to make the point that in a fairly new transformer, the
presence of any acetylene would give rise to concern, but in a 20 year old
transformer the gas levels quoted in the table, including acetylene, would
not be considered extraordinary.
==============
 Table 16 IEEE criteria for classification of risks to transformers based
on d.g.a. sample analysis when there is no previous d.g.a. history.
Condition 1 TDCG below this level indicates the transformer is operating satisfactorily.
Any individual combustible gas exceeding specified levels should prompt additional
investigation.
Condition 2 TDCG within this range indicates greater than normal combustible
gas level.
Any individual combustible gas exceeding specified levels should prompt additional
investigation. Action should be taken to establish a trend. Fault(s) may be
present.
Condition 3 TDCG within this range indicates a high level of decomposition.
Any individual combustible gas exceeding specified levels should prompt additional
investigation.
Immediate action should be taken to establish a trend. Fault(s) are probably
present.
Condition 4 TDCG within this range indicates excessive decomposition. Continued
operation could result in failure of the transformer.
==========
In the UK the organization EA Technology's Dr M.K Domun studied and collated
oil analysis data from around 500 transformers, mainly of 132 kV, for many
years and as a result of this work published figures in a paper presented to
an IEE Conference on Dielectric Materials, Measurements and Applications in
September, 1992, [6.11] as 'optimal values' for transformers which have been
on load for a lengthy period and which are considered to be in a 'healthy'
condition. These are listed in Table 17.
============

Table 17 M.K. Domun's norms for dissolved gas levels in system transformers
Hydrogen 20 ppm Methane 10 ppm Ethane 10 ppm Ethylene 10 ppm Acetylene 1 ppm
Carbon dioxide 5 000 ppm Carbon monoxide 100 ppm Acidity 0.08 mgKOH/g Moisture
25 ppm (no temperature quoted) Electric strength 27 kV Furfuraldehyde 2 mg/l
============
It will be noted that Dr Domun's norms are somewhat less than those suggested
by IEEE. Dr Domun stresses that there is a wide variation between individual
units and says that the above figures were chosen on the basis of the 50 percent
rule, i.e. at least 50 percent of the samples conform to the values of these
parameters. CEGB experience is of large generator transformers which are operated
at high loadings for long periods, unlike the network transformers studied
by Dr Domun, and many of these continued to operate satisfactorily with hydrocarbon
gas levels considerably higher than the values given Table 17.
The above examples illustrate both the disadvantage of aiming to identify
norms as well as the benefit. It is with this note of caution that the norms
in Tables 15 and 17 are provided.
It should be noted that, at the time of writing this Thirteenth edition, IEEE
C57.104 is under revision.
Other monitoring systems
Put into the simplest terms it can be said that transformers have three basic
failure modes:
• They can suffer insulation failure leading to electrical breakdown between
internal parts.
• They can fail due to severe internal overheating.
• They can suffer mechanical failure due to their inability to withstand the
effects of a close-up external fault.
It is the first two of these modes which are truly 'faults' for which dissolved
gas analysis can be of assistance in providing indication of incipient break
down before this has reached the catastrophic stage. But it is the third which
represents 'end of life' failure. When paper insulation is severely degraded
it loses its mechanical strength but nevertheless much of the dielectric strength
of the paper/oil combination is retained so that in a transformer of which
the insulation has aged to the extent of approaching the end of its useful
life, there is no immediate failure and the transformer will continue to operate
satisfactorily until it receives a 'shock' mechanical loading due to some external
factor such as a system fault relatively close to its terminals. Ideally a
user would like to replace his transformer just before it is due to fail in
this way. If he replaces it several years before it is due to fail he has not
obtained maximum use and there will be an economic 'cost.' If he defers replacement
until failure has actually occurred he is involved in the high costs of an
unscheduled outage and the need to find a replacement on an urgent basis, and
possibly even some consequential damage costs.
Consideration of this problem has engaged researchers for some years; to find
a system of knowing just when insulation has reached the point when it no longer
has sufficient strength to meet the mechanical demands placed upon it. It was
hoped at the early stages of developing furfuraldehyde assessment that this
might be linked to the absolute level of paper degradation and thus provide
the means that were sought, but there are problems in attempting to derive
absolute indications from furfuraldehyde in exactly the same way as there are
from the hydrocarbon gases. Transformers vary so considerably in their relative
insulation volumes, oil content, water content and acidity as well as loading
patterns, and all these factors influence furfuraldehyde levels. In addition,
the degradation of a fairly small localized area of insulation in the vicinity
of a hot spot can be just as terminal as degradation of far greater extent
in a design which has seen extensive service but which does not have significant
hot spots The former, how ever, will generate a far smaller quantity of furfuraldehyde
making it much more likely to go undetected. As indicated in Section 3, the
properties of paper insulation depend on those of the long chain cellulose
molecules of which it is made up. Deterioration of its mechanical properties
is brought about by decomposition of these long chain molecules, and early
researchers used tensile strength as a measure of remanent life. Current practice
is to measure degree of polymerization (DP) which is an indication of the number
'links' in the long chain cellulose molecules. This starts at about 1100-1200
for new material but drops rapidly during the drying and processing stage of
the transformer to around 850-900 which might be taken as a typical starting
point for a new transformer.
End of life is reached when DP has dropped to about 250 and the paper loses
its remaining strength suddenly at about half of its original value.
There have been suggestions that by entering the transformer and taking samples
of the insulation for measurement of DP, the remanent life of the insulation
could be estimated. The problem, of course, is that any insulation which is
sufficiently accessible to sample will not be representative of the more critical
insulation in the vicinity of the hot spot. One way of overcoming this would
be to place an insulation sample in the hottest oil at the time of commissioning
the transformer and to further heat this by means of a heater coil supplied
from a current transformer placed in one of the winding leads in the same way
as for a thermal image winding temperature indicator. The
difficulty is that the hot spot temperature cannot be determined with sufficient
accuracy to make this exercise worthwhile. The problem remains, therefore,
that determination of imminent end of life must be based on little more than
guesswork.
Another approach thought by a number of researchers to have promise is based
on the detection of movement within the windings in response to impressed low-voltage
impulses. As insulation ages, shrinkage occurs so that, whilst windings are
initially in a state of axial compression due to the manufacturing clamping
forces, as end of life is approached the effect of shrinkage will create a
degree of slackness. The slackness, of itself, can accelerate the onset of
failure of a transformer already weakened by the low mechanical strength of
its insulation, since it will permit winding displacement and, as explained
in Section 4.7, the axial forces on the transformer windings under high through
fault currents are increased if there is already some initial displacement.
Most of the methods employed require the transformer to be taken entirely off-line
so as to avoid the presence of an external circuit making the difficult task
of detection of the impulse currents and the small changes in them even more
difficult. Other systems have attempted to detect winding vibration produced
by the impulses, using acoustic sensors. Another technique is based on the
fact that the slight change in winding inductance and capacitance values will
result in changes to natural resonance frequencies. The difficulty with all
of these efforts is in relating the measured parameters to transformer condition
and the risk of failure. Accurate measurement of the selected parameter is
itself difficult enough but making this final step is many times more so and
it is unlikely that such methods will achieve meaningful results in the foreseeable
future so that meanwhile the guesswork must continue.
Failures and their causes
In the foregoing paragraphs there has been a general discussion of the mechanisms
of transformer failure. Earlier editions of this volume have included a more
specific catalogue of the ways in which transformers have failed in service.
Such an approach was reasonable in the earliest editions, since transformer
design and manufacture was developing rapidly and those involved in the process
were going through a phase of gaining a large amount of experience with regard
to what could be done and what could not. Hopefully, more than 80 years after
the publication of the first edition, this experience has been fully assimilated,
failure rates have been reduced significantly and to simply include a list
of failures which have occurred over the past 20 years is likely to teach very
little. Designs have changed and a transformer built today will have many different
features from one made 20 years ago, although it might appear superficially
the same. For example, in earlier editions failure of core bolt insulation
was identified as a common fault. For a purchaser to use this knowledge at
the present time to specify the quality of core-bolt insulation, or even to
insist that bolted cores should be avoided, would be superfluous, since small
and medium sized transformers have used boltless cores for many years and core-bolts
are now avoided in even the largest cores.
This is not to say that failures will cease to happen. Relatively recently,
in the early 1970s, CEGB noted disturbingly high failure rates in large generator
transformers. (This has also been discussed in Section 5.3). There were a number
of reasons for this but significant amongst these was the large step increase
in unit sizes as generator ratings were rapidly increased in the UK from around
120 MW to 500 and 660 MW. Failure rates were reduced once more in the 1980s
by a combination of more extensive testing, improved QA during manufacture,
moving to single-phase units rather than three phase, which had the effect
of removing the severe limitations which the latter had imposed on transport
weights, thus reducing the loadings imposed on the basic materials, and also
by adopting a procedure whereby designs which had been proven by service were
repeated, rather than accepting a process of almost continual innovation.
This latter strategy was controversial, since limiting innovation can be construed
as preventing manufacturers using their skills to increase their competitiveness.
However the same accusation can be leveled at the practice referred to earlier
of listing previous failures and their causes, since there is an inference
that if such a way of doing something has caused a failure in the past, then
this should always be avoided in the future regardless of the availability
of improved materials and better methods of performing design calculations,
and this can lead to very restrictive thinking. It can also result in purchasers'
specifications becoming very proscriptive. This is a criticism which was often
made of the UK Electricity Supply Industries' Specification BEBS T2 (1966),
and indeed, this document identified many design and construction features
which it considered unacceptable, usually because they had caused failure at
some time in the past.
Now the move is towards specifications which allow manufacturers to utilize
their own design skills. But if they are to be given this freedom, specifications
must also call for adequate testing and they must also tell manufacturers exactly
how the transformer is to be operated. Section 8.1 deals with the specification
of technical requirements and it is hoped that this will enable prospective
purchasers to identify all those operational features which have a bearing
on how a transformer should be designed and manufactured. The reasons why these
particular features are relevant should, of course, be apparent from else where
within the pages of this guide.
Clearly, not all transformer failures are the fault of the designer or manufacturer.
Operation and maintenance must also have an impact as it is hoped will be appreciated
from a study of the earlier part of this section. Although maintenance requirements
are few, users must regularly monitor the condition of their transformer and,
if they seek high reliability, they must ensure that three fundamental requirements
are observed:
• Breather systems must be adequately maintained so that water content is
kept at the lowest practicable level.
• The transformer must be adequately cooled at all times, any overloading
maintained within permitted limits and action taken on any indications of possible
overheating.
• The transformer must not be subjected to excessive overvoltages.
One of the most detailed international studies of transformer failures was
carried out by a CIGRE Working Group in 1978. It was reported in Electra number
88, dated May, 1983 [6.12]. Input was received from 13 countries relating to
all types of transformers having HV voltages from 72 to 765 kV. The analysis
took account of more than 1000 failures occurring between 1968 and 1978, relating
to a total population of more than 47 000 unit-years. The transformers varied
from 'just entered service' to 'aged 20 years.' Nearly half were aged between
10 and 20 years. They were categorized into power station transformers, substation
transformers and autotransformers and were further subdivided into those with
on-load tapchangers (OLTC) and those without. The main purpose of the survey
was to establish reliability figures, but those responding to the questionnaires
were also asked to categorize the reasons for failure. The overall failure
rate was concluded to be 2 percent and the breakdown into voltage classes showed
that the figure was higher, up to 3 percent, for the 300-700 kV voltage class.
Figures for the greater than 700 kV class were left out of the main report
since too few statistics were reported. These were covered in an appendix in
which it was reported that the failure rate was about 7 percent.

FIG. 128 Substation transformers. Failures with forced and scheduled outage.
Units with on-load tapchanger. Population: 31031 Unit-years
FIG. 128, reproduced from the report, shows the causes of failure for
the largest group, covering over 31 000 unit-years. These are substation transformers
with on-load tapchangers, and the pattern is similar for other groups.
The histogram gives the presumed cause of failure, the component involved
and the type of failure. The quantities also indicate the outage time involved,
classified as either less than one day, 1-30 days or greater than 30 days.
The most significant features to emerge are that the on-load tapchanger was
the component most frequently involved, perhaps not too surprising since this
is the only component of the transformer which has moving parts; with winding
faults less than half as frequent but still the second most likely component
to fail. For all groups the magnetic circuit has the lowest reported failure
rate, this despite the fact that the statistics refer to transformers in service
between 1968 and 1978 when the use of bolted-cores was standard practice. Although
design and manufacturing errors were reported as by far the most likely cause
of failure, it should be noted that incorrect maintenance figures quite prominently
in this list of causes. (It must be remembered that this information has been
provided by the transformer operators.)

FIG. 129 Power station transformers. Failures with forced and scheduled
outage. Units with on-load tapchanger. Population: 2335 Unit-years.
FIG. 129 gives the reported data for the equivalent group of power station
transformers, namely those with on-load tapchangers. This is a very much smaller
group, covering only just over 2300 unit-years so the figures must be correspondingly
less reliable. The largely similar pattern is nevertheless evident, except
that terminals now become the most likely component to fail, equally with windings.
This probably reflects the fact that power station transformers tend to run
more fully loaded so that components such as terminals will be more highly
stressed. What is surprising is that terminal failures almost invariably resulted
in outages exceeding one day and a significant proportion of outages exceeded
30 days so these must have been more serious than simply requiring changing
of a bushing. This does emphasize the importance of paying proper attention
to the selection and installation of these components and of ensuring that
connections are correctly made and checked during maintenance. The very much
lower ranking of tapchanger related faults probably reflects the fact that
on generator transformers these operate on manual control and perform far fewer
operations than those of substation transformers which are under automatic
control.
|